RFC 7460

Monitoring and Control MIB for Power and Energy

๐Ÿ“… published March 2015, from ietf

RFC 7460: Monitoring and Control MIB for Power and Energy โšก

okay bestie, this one is RFC 7460 ๐Ÿ’–, a Standards Track doc from the IETF, published in March 2015 ๐Ÿ“…. It's ISSN: 2070-1721 and it was written by M. Chandramouli, B. Claise, B. Schoening, J. Quittek, and T. Dietz ๐Ÿซถ. Chandramouli and Claise are at Cisco Systems, Inc., Schoening is an Independent Consultant, and Quittek and Dietz are at NEC Europe, Ltd. ๐ŸŒธ

Abstract

so the whole point of this doc is that it defines a subset of the Management Information Base (MIB) for power and energy monitoring of devices โšก๐Ÿ”‹

Status of This Memo

this is an Internet Standards Track document ๐Ÿ’…

it's a product of the Internet Engineering Task Force (IETF), so it represents the consensus of the IETF community โœจ. it got public review and was approved for publication by the Internet Engineering Steering Group (IESG) ๐Ÿ‘‘. if you want more on Internet Standards, check out Section 2 of RFC 5741 ๐Ÿ“š.

info about the current status of this doc, any errata, and how to send feedback is over at http://www.rfc-editor.org/info/rfc7460 ๐Ÿฆ‹

Copyright (c) 2015 IETF Trust and the persons identified as the document authors. All rights reserved. ยฉ๏ธ๐ŸŽ€

this doc is subject to BCP 78 and the IETF Trust's Legal Provisions Relating to IETF Documents (http://trustee.ietf.org/license-info) as they stand on the date it was published. please actually read these, bestie, because they explain your rights and restrictions for this doc ๐Ÿ™ˆ. any Code Components pulled out of this doc must include Simplified BSD License text, as described in Section 4.e of the Trust Legal Provisions, and they come without warranty, as the Simplified BSD License describes ๐Ÿ’œ.

Table of Contents

1. Introduction ....................................................3
   1.1. Conventions Used in This Document ..........................3
2. The Internet-Standard Management Framework ......................3
3. Use Cases .......................................................4
4. Terminology .....................................................4
5. Architecture Concepts Applied to the MIB Modules ................5
   5.1. Energy Object Tables .......................................5
        5.1.1. ENERGY-OBJECT-MIB ...................................5
        5.1.2. POWER-ATTRIBUTES-MIB ................................7
        5.1.3. UML Diagram .........................................9
   5.2. Energy Object Identity ....................................12
   5.3. Power State ...............................................12
        5.3.1. Power State Set ....................................13
   5.4. Energy Object Usage Information ...........................13
   5.5. Optional Power Usage Attributes ...........................14
   5.6. Optional Energy Measurement ...............................14
   5.7. Fault Management ..........................................18
6. Discovery ......................................................18
7. Link with the Other IETF MIBs ..................................19
   7.1. Link with the ENTITY-MIB and the ENTITY-SENSOR MIB ........19
   7.2. Link with the ENTITY-STATE MIB ............................20
   7.3. Link with the POWER-OVER-ETHERNET MIB .....................21
   7.4. Link with the UPS MIB .....................................21
   7.5. Link with the LLDP and LLDP-MED MIBs ......................22
8. Structure of the MIB ...........................................23
9. MIB Definitions ................................................24
   9.1. The IANAPowerStateSet-MIB Module ..........................24
   9.2. The ENERGY-OBJECT-MIB MIB Module ..........................27
   9.3. The POWER-ATTRIBUTES-MIB MIB Module .......................50
10. Security Considerations .......................................63
11. IANA Considerations ...........................................64
   11.1. IANAPowerStateSet-MIB Module .............................65
12. References ....................................................65
   12.1. Normative References .....................................65
   12.2. Informative References ...................................66
Acknowledgments ...................................................68
Contributors ......................................................68
Authors' Addresses ................................................69

1. Introduction โœจ

okay so this doc defines a subset of the Management Information Base (MIB) for use in energy management of devices within or connected to communication networks ๐Ÿ”Œ. the MIB modules here are designed to give us a model for energy management, and that covers monitoring Power State and energy consumption of networked elements ๐Ÿงš. this MIB takes the "Energy Management Framework" [RFC7326] into account, and that framework is itself based on the "Requirements for Energy Management" [RFC6988] ๐Ÿ’….

energy management can be applied to devices in communication networks, and the target devices here include (but are not limited to) routers, switches, Power over Ethernet (PoE) endpoints, protocol gateways for building management systems, intelligent meters, home energy gateways, hosts and servers, sensor proxies, etc. ๐ŸŒˆ the target devices and use cases for Energy Management are covered in Energy Management Applicability Statement [EMAN-AS] ๐Ÿ“š.

where it makes sense, device monitoring reaches the individual components of the device and any attached dependent devices ๐ŸŽ€. for example, a device can have components that are independent from a Power State point of view, like line cards, processor cards, and hard drives. a device can also have dependent attached devices, like a switch with PoE endpoints or a power distribution unit with attached endpoints ๐Ÿฆ‹.

1.1. Conventions Used in This Document ๐Ÿ’œ

the key words "MUST", "MUST NOT", "REQUIRED", "SHALL", "SHALL NOT", "SHOULD", "SHOULD NOT", "RECOMMENDED", "NOT RECOMMENDED", "MAY", and "OPTIONAL" in this document are to be interpreted as described in RFC 2119 [RFC2119] ๐Ÿ”ฅ. these are the official requirement words, so read them carefully bestie ๐Ÿ™ˆ.

2. The Internet-Standard Management Framework ๐Ÿ“

for a detailed overview of the docs that describe the current Internet-Standard Management Framework, go look at section 7 of RFC 3410 [RFC3410] ๐Ÿ“–.

managed objects are accessed through a virtual information store called the Management Information Base, or MIB ๐Ÿ—‚๏ธ. MIB objects are usually accessed through the Simple Network Management Protocol (SNMP) ๐Ÿ›ฐ๏ธ. objects in the MIB are defined with the mechanisms in the Structure of Management Information (SMI) ๐Ÿงฉ. this memo specifies MIB modules that are compliant to SMIv2, which is described in STD 58, RFC 2578 [RFC2578], STD 58, RFC 2579 [RFC2579] and STD 58, RFC 2580 [RFC2580] โœจ.

3. Use Cases ๐ŸŒธ

requirements for power and energy monitoring of networking devices are specified in [RFC6988]. those requirements cover devices typically found in communications networks, like switches, routers, and various connected endpoints ๐Ÿ”Œ. for a power monitoring architecture to be useful, it should also apply to facility meters, power distribution units, gateway proxies for commercial building control, home automation devices, and devices that interface with the utility and/or smart grid โšก. so the scope of the MIB modules in this document is broader than what [RFC6988] specifies ๐Ÿ‘‘. several use cases for Energy Management have been identified in the "Energy Management (EMAN) Applicability Statement" [EMAN-AS] ๐Ÿ’–.

4. Terminology ๐Ÿงš

please refer to [RFC7326] for the definitions of the following terminology used in this document ๐Ÿ“š:

   Energy Management
   Energy Management System (EnMS)
   Energy Monitoring
   Energy Control
   electrical equipment
   non-electrical equipment (mechanical equipment)
   device
   component
   power inlet
   power outlet
   energy
   power
   demand
   provide energy
   receive energy
   meter (energy meter)
   battery
   Power Interface
   Nameplate Power
   Power Attributes
   Power Quality
   Power State
   Power State Set

5. Architecture Concepts Applied to the MIB Modules ๐Ÿฆ‹

this section describes the concepts from the Energy Management Framework [RFC7326] that relate to power usage, with specific info about the MIB module in this document ๐Ÿ’…. this subsection maps concepts developed in the Energy Management Framework [RFC7326] ๐ŸŒˆ.

the Energy Monitoring MIB has two independent MIB modules: ENERGY-OBJECT-MIB and POWER-ATTRIBUTES-MIB ๐Ÿ”‹. the first, ENERGY-OBJECT-MIB, is focused on measuring power and energy โšก. the second, POWER-ATTRIBUTES-MIB, is focused on power quality measurements for Energy Objects โœจ.

devices and their sub-components can be modeled using the containment tree of the ENTITY-MIB [RFC6933] ๐ŸŽ€.

5.1. Energy Object Tables ๐Ÿ’–

5.1.1. ENERGY-OBJECT-MIB โœจ

okay so the ENERGY-OBJECT-MIB module is made of five tables ๐Ÿ’… let's go through them!

The first one is the eoMeterCapabilitiesTable ๐ŸŽ€. It tells you what instrumentation each Energy Object has. Each entry says which of the other tables from ENERGY-OBJECT-MIB and POWER-ATTRIBUTES-MIB are available for that Energy Object. It's indexed by entPhysicalIndex [RFC6933].

The second is the eoPowerTable ๐Ÿ”ฅ. It reports how much power each Energy Object is consuming, plus the units, sign, measurement accuracy, and related objects. It's indexed by entPhysicalIndex.

The third is the eoPowerStateTable ๐Ÿฆ‹. For each Energy Object, it shows info and stats about the Power States it supports. It's indexed by entPhysicalIndex and eoPowerStateIndex, so it's giving two-key energy ๐Ÿ’œ.

The fourth is the eoEnergyParametersTable โš™๏ธ. The entries here configure the parameters for energy and demand measurement collection. It's indexed by eoEnergyParametersIndex.

The fifth is the eoEnergyTable ๐Ÿ“–. This one holds a log of the energy and demand info. It's also indexed by eoEnergyParametersIndex, so it's lowkey the diary of the whole module ๐Ÿงš.

Okay, now the tree ๐ŸŒณ. It's a "smidump-style" presentation of the MIB modules in this document. The three symbols are a compressed way of showing each object's MAX-ACCESS clause, and they map like this:

"not-accessible"         ->  "---"
"accessible-for-notify"  ->  "--n"
"read-only"              ->  "r-n"
"read-write"             ->  "rwn"

Here's the whole tree, slay ๐Ÿ’–:

  eoMeterCapabilitiesTable(1)
   |
   +---eoMeterCapabilitiesEntry(1)[entPhysicalIndex]
   |   |
   |   +---r-n  BITS             eoMeterCapability
   |

  eoPowerTable(2)
   |
   +---eoPowerEntry(1) [entPhysicalIndex]
   |   |
   |   +---r-n Integer32         eoPower(1)
   |   +-- r-n Unsigned32        eoPowerNamePlate(2)
   |   +-- r-n UnitMultiplier    eoPowerUnitMultiplier(3)
   |   +-- r-n Integer32         eoPowerAccuracy(4)
   |   +-- r-n INTEGER           eoPowerMeasurementCaliber(5)
   |   +-- r-n INTEGER           eoPowerCurrentType(6)
   |   +-- r-n TruthValue        eoPowerMeasurementLocal(7)
   |   +-- rwn PowerStateSet     eoPowerAdminState(8)
   |   +-- r-n PowerStateSet     eoPowerOperState(9)
   |   +-- r-n OwnerString       eoPowerStateEnterReason(10)
   |
   |
   |
   +---eoPowerStateTable(3)
   |
   |      +--eoPowerStateEntry(1)
   |      |     [entPhysicalIndex, eoPowerStateIndex]
   |      |
   |      +-- --n PowerStateSet eoPowerStateIndex(1)
   |      +-- r-n Integer32         eoPowerStateMaxPower(2)
   |      +-- r-n UnitMultiplier
   |                      eoPowerStatePowerUnitMultiplier(3)
   |      +-- r-n TimeTicks         eoPowerStateTotalTime(4)
   |      +-- r-n Counter32         eoPowerStateEnterCount(5)
   |
   +eoEnergyParametersTable(4)
   |
   +---eoEnergyParametersEntry(1) [eoEnergyParametersIndex]
   |
   |   +-- --n PhysicalIndex  eoEnergyObjectIndex(1)
   |   +   r-n Integer32      eoEnergyParametersIndex(2)
   |   +-- rwn TimeInterval   eoEnergyParametersIntervalLength(3)
   |   +-- rwn Unsigned32     eoEnergyParametersIntervalNumber(4)
   |   +-- rwn INTEGER        eoEnergyParametersIntervalMode(5)
   |   +-- rwn TimeInterval   eoEnergyParametersIntervalWindow(6)
   |   +-- rwn Unsigned32     eoEnergyParametersSampleRate(7)
   |   +-- rwn StorageType    eoEnergyParametersStorageType(8)
   |   +-- rwn RowStatus      eoEnergyParametersStatus(9)
   |
   +eoEnergyTable(5)
   |
   +---eoEnergyEntry(1)
   |    [eoEnergyParametersIndex,eoEnergyCollectionStartTime]
   |
   |   +-- r-n TimeTicks      eoEnergyCollectionStartTime(1)
   |   +-- r-n Unsigned32     eoEnergyConsumed(2)
   |   +-- r-n Unsigned32     eoEnergyProvided(3)
   |   +-- r-n Unsigned32     eoEnergyStored(4)
   |   +-- r-n UnitMultiplier eoEnergyUnitMultiplier(5)
   |   +-- r-n Integer32      eoEnergyAccuracy(6)
   |   +-- r-n Unsigned32     eoEnergyMaxConsumed(7)
   |   +-- r-n Unsigned32     eoEnergyMaxProduced(8)
   |   +-- r-n TimeTicks      eoEnergyDiscontinuityTime(9)

5.1.2. POWER-ATTRIBUTES-MIB ๐ŸŒˆ

The POWER-ATTRIBUTES-MIB module has three tables โญ.

The first is the eoACPwrAttributesTable ๐Ÿ”Œ. It shows the power quality available for each Energy Object. It's indexed by entPhysicalIndex [RFC6933].

The second is the eoACPwrAttributesDelPhaseTable ๐ŸŒธ. Its entries are meant to configure the parameters of energy and demand measurement collection, and it's indexed by eoEnergyParametersIndex. ngl this one's a bit of a plot twist ๐Ÿ™ˆ.

The third is the eoACPwrAttributesWyePhaseTable ๐Ÿ“. For each Energy Object, it reports info and stats about the supported Power States. It's indexed by entPhysicalIndex and eoPowerStateIndex. yes, it says eoPowerStateTable there, and yes, that's how the original reads ๐Ÿ’€.

Here's the tree for these tables, bestie ๐Ÿซถ:

  eoACPwrAttributesTable(1)
    |
    +---eoACPwrAttributesEntry(1) [ entPhysicalIndex]
    |   |
    |   +---r-n INTEGER    eoACPwrAttributesConfiguration(1)
    |   +-- r-n Integer32  eoACPwrAttributesAvgVoltage(2)
    |   +-- r-n Unsigned32 eoACPwrAttributesAvgCurrent(3)
    |   +-- r-n Integer32  eoACPwrAttributesFrequency(4)
    |   +-- r-n UnitMultiplier
    |                eoACPwrAttributesPowerUnitMultiplier(5)
    |   +-- r-n Integer32  eoACPwrAttributesPowerAccuracy(6)
    |   +-- r-n Integer32
    |                   eoACPwrAttributesTotalActivePower(7)
    |   +-- r-n Integer32
    |                 eoACPwrAttributesTotalReactivePower(8)
    |   +-- r-n Integer32
    |                 eoACPwrAttributesTotalApparentPower(9)
    |   +-- r-n Integer32
    |                  eoACPwrAttributesTotalPowerFactor(10)
    |   +-- r-n Integer32  eoACPwrAttributesThdCurrent(11)
    |   +-- r-n Integer32  eoACPwrAttributesThdVoltage(12)
    |
    +eoACPwrAttributesDelPhaseTable(2)
    |
    +-- eoACPwrAttributesDelPhaseEntry(1)
    |     |   [entPhysicalIndex, eoACPwrAttributesDelPhaseIndex]
    |     |
    |     +-- r-n Integer32
    |     |    eoACPwrAttributesDelPhaseIndex(1)
    |     +-- r-n Integer32
    |     |    eoACPwrAttributesDelPhaseToNextPhaseVoltage(2)
    |     +-- r-n Integer32
    |     | eoACPwrAttributesDelThdPhaseToNextPhaseVoltage(3)
    |     |
    +eoACPwrAttributesWyePhaseTable(3)
    |
    +-- eoACPwrAttributesWyePhaseEntry(1)
    |     |   [entPhysicalIndex, eoACPwrAttributesWyePhaseIndex]
    |     |
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyePhaseIndex(1)
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyePhaseToNeutralVoltage(2)
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyeCurrent(3)
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyeActivePower(4)
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyeReactivePower(5)
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyeApparentPower(6)
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyePowerFactor(7)
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyeThdCurrent(9)
    |     +-- r-n Integer32
    |     |     eoACPwrAttributesWyeThdPhaseToNeutralVoltage(10)

5.1.3. UML Diagram โœจ

okay so bestie, this is the UML diagram ๐Ÿฆ‹ It's a visual map of every MIB object in the two modules, ENERGY-OBJECT-MIB and POWER-ATTRIBUTES-MIB, so you can literally see how everything connects ๐Ÿ’–

         +-----------------------+
         | Meter Capabilities    |
         | --------------------- |
         | eoMeterCapability     |
         +-----------------------+

         +-----------------------+
   |---> |  Energy Object ID (*) |
   |     | --------------------- |
   |     | entPhysicalIndex      |
   |     | entPhysicalClass      |
   |     | entPhysicalName       |
   |     | entPhysicalUUID       |
   |     +-----------------------+
   |
   |     +---------------------------+
   |---- |_ Power Table              |
   |     | ------------------------- |
   |     | eoPower                   |
   |     | eoPowerNamePlate          |
   |     | eoPowerUnitMultiplier     |
   |     | eoPowerAccuracy           |
   |     | eoPowerMeasurementCaliber |
   |     | eoPowerCurrentType        |
   |     | eoPowerMeasurementLocal   |
   |     | eoPowerAdminState         |
   |     | eoPowerOperState          |
   |     | eoPowerStateEnterReason   |
   |     +---------------------------+
   |     +---------------------------------+
   |---- |_Energy Object State Statistics  |
   |     |-------------------------------- |
   |     | eoPowerStateIndex               |
   |     | eoPowerStateMaxPower            |
   |     | eoPowerStatePowerUnitMultiplier |
   |     | eoPowerStateTotalTime           |
   |     | eoPowerStateEnterCount          |
   |     +---------------------------------+
   |
   |     +----------------------------------+
   |---- |    Energy ParametersTable        |
   |     | -------------------------------- |
   |     | eoEnergyObjectIndex              |
   |     | eoEnergyParametersIndex          |
   |     | eoEnergyParametersIntervalLength |
   |     | eoEnergyParametersIntervalNumber |
   |     | eoEnergyParametersIntervalMode   |
   |     | eoEnergyParametersIntervalWindow |
   |     | eoEnergyParametersSampleRate     |
   |     | eoEnergyParametersStorageType    |
   |     | eoEnergyParametersStatus         |
   |     +----------------------------------+
   |
   |     +----------------------------------+
   |---- |    Energy Table                  |
         | -------------------------------- |
         | eoEnergyCollectionStartTime      |
         | eoEnergyConsumed                 |
         | eoEnergyProvided                 |
         | eoEnergyStored                   |
         | eoEnergyUnitMultiplier           |
         | eoEnergyAccuracy                 |
         | eoEnergyMaxConsumed              |
         | eoEnergyMaxProduced              |
         | eoDiscontinuityTime              |
         +----------------------------------+

      Figure 1: UML Diagram for energyObjectMib

Figure 1: UML Diagram for energyObjectMib ๐ŸŒˆ

(*) Compliance with the ENERGY-OBJECT-CONTEXT-MIB ๐Ÿ’…

         +-----------------------+
   |---> |  Energy Object ID (*) |
   |     | --------------------- |
   |     | entPhysicalIndex      |
   |     | entPhysicalName       |
   |     | entPhysicalUUID       |
   |     +-----------------------+
   |     +--------------------------------------+
   |---- |  Power Attributes                    |
   |     | ------------------------------------ |
   |     | eoACPwrAttributesConfiguration       |
   |     | eoACPwrAttributesAvgVoltage          |
   |     | eoACPwrAttributesAvgCurrent          |
   |     | eoACPwrAttributesFrequency           |
   |     | eoACPwrAttributesPowerUnitMultiplier |
   |     | eoACPwrAttributesPowerAccuracy       |
   |     | eoACPwrAttributesTotalActivePower    |
   |     | eoACPwrAttributesTotalReactivePower  |
   |     | eoACPwrAttributesTotalApparentPower  |
   |     | eoACPwrAttributesTotalPowerFactor    |
   |     | eoACPwrAttributesThdCurrent          |
   |     | eoACPwrAttributesThdVoltage          |
   |     +--------------------------------------+
   |     +------------------------------------------------+
   |---- |  AC Input DEL Configuration                    |
   |     | ---------------------------------------------- |
   |     | eoACPwrAttributesDelPhaseIndex                 |
   |     | eoACPwrAttributesDelPhaseToNextPhaseVoltage    |
   |     | eoACPwrAttributesDelThdPhaseToNextPhaseVoltage |
   |     +------------------------------------------------+
   |
   |     +----------------------------------------------+
   |---- |  AC Input WYE Configuration                  |
         | -------------------------------------------- |
         | eoACPwrAttributesWyePhaseIndex               |
         | eoACPwrAttributesWyePhaseToNeutralVoltage    |
         | eoACPwrAttributesWyeCurrent                  |
         | eoACPwrAttributesWyeActivePower              |
         | eoACPwrAttributesWyeReactivePower            |
         | eoACPwrAttributesWyeApparentPower            |
         | eoACPwrAttributesWyePowerFactor              |
         | eoACPwrAttributesWyeThdCurrent               |
         | eoACPwrAttributesWyeThdPhaseToNeutralVoltage |
         +----------------------------------------------+

        Figure 2: UML Diagram for the POWER-ATTRIBUTES-MIB

        (*) Compliance with the ENERGY-OBJECT-CONTEXT-MIB

Figure 2: UML Diagram for the POWER-ATTRIBUTES-MIB ๐ŸŽ€

(*) Compliance with the ENERGY-OBJECT-CONTEXT-MIB ๐Ÿ’œ


5.2. Energy Object Identity ๐ŸŒธ

so the Energy Object identity info lives in the primary table of the ENERGY-OBJECT-CONTEXT-MIB module [RFC7461], which is the eoTable ๐Ÿ“‹ That's where you find the Energy Object context, like its domain, role description, and importance. The ENERGY-OBJECT-CONTEXT-MIB module also spells out how Energy Objects relate to each other. There are several possible relationships, including meteredBy, metering, poweredBy, powering, aggregatedBy, and aggregating, and they're defined in the IANA-ENERGY-RELATION-MIB module [RFC7461] โญ

5.3. Power State ๐Ÿ”‹

so an Energy Object can have energy-conservation modes called "Power States" ๐ŸŒ™ There can be a bunch of in-between energy-saving modes between fully ON and fully OFF.

The universal power management states of an Energy Object live in the eoPowerState MIB object. The state it's actually in is the eoPowerOperState MIB object, and the eoPowerAdminState MIB object holds the Power State that was requested for it ๐ŸŽฏ If those two values don't match, that means the Energy Object is busy switching from eoPowerAdminState over to eoPowerOperState, and once it's done, it updates eoPowerOperState. The reason for a Power State change gets reported in eoPowerStateEnterReason. For that one, management stations and Energy Objects should support any owner string format the organization's local policy calls for. It's suggested that this name include at least the reason for the change, plus one or more of these: IP address, management station name, network manager's name, location, or phone number ๐Ÿ“ž

The eoPowerOperState, eoPowerAdminState, and eoPowerStateEnterReason objects are all in the eoPowerTable ๐Ÿ—‚๏ธ

eoPowerStateTable lists the maximum power usage in watts for every single supported Power State of each Power State Set the Energy Object supports ๐Ÿ’ก It also gives you extra stats, like eoPowerStateEnterCount (how many times an entity has visited a particular Power State) and eoPowerStateTotalTime (the total time spent in a particular Power State of an Energy Object) โฑ๏ธ

5.3.1. Power State Set ๐Ÿงฉ

there are a bunch of standards and implementations of Power State Sets, and an Energy Object can support one or several of them at the same time ๐Ÿซถ

right now there are three Power State Sets defined:

   IEEE1621(256) - [IEEE1621]
   DMTF(512)     - [DMTF]
   EMAN(768)     - [RFC7326]

The Power State Sets are listed in [RFC7326] along with each Power State inside each set โœจ They're specified by the PowerStateSet Textual Convention (TC), which is an IANA-maintained MIB module. The first version of this MIB module is specified in this document ๐ŸŒˆ

5.4. Energy Object Usage Information โšก

for an Energy Object, power usage gets reported using eoPower ๐Ÿ”Œ The magnitude is based on the eoPowerUnitMultiplier MIB variable, which uses the UnitMultiplier TC. Power measurement magnitude should conform to the unit multiplier definitions for SI units in IEC 62053-21 [IEC.62053-21] and IEC 62053-22 [IEC.62053-22] (SI meaning the International System of Units) ๐Ÿงฎ Measured values come out in SI units as BaseValue * 10 raised to the power of the unit multiplier.

For example, if an Energy Object's current power usage is 3, it could be 3 W, 3 mW, 3 kW, or 3 MW, depending on eoPowerUnitMultiplier ๐Ÿ˜ญ Other measurements in these two MIB modules use the same mechanism too, including eoPowerStatePowerUnitMultiplier, eoEnergyUnitMultiplier, and oACPwrAttributesPowerUnitMultiplier.

It's also really useful to know how an eoPower measurement was obtained ๐Ÿ•ต๏ธโ€โ™€๏ธ A Network Management System (NMS) can use that to account for the accuracy and nature of readings across different implementations. eoPowerMeasurementLocal says whether the measurements were taken at the device itself or from a remote source. eoPowerMeasurementCaliber describes the method used to measure the power, and it can tell actual values apart from estimated ones. Some devices in the network might not be able to measure or report power consumption at all ๐Ÿ’€ For those, eoPowerMeasurementCaliber shall report that the measurement mechanism is "unavailable", and the eoPower measurement shall be "0".

The nameplate power rating of an Energy Object is in the eoPowerNameplate MIB object ๐Ÿท๏ธ

5.5. Optional Power Usage Attributes ๐ŸŽ€

the optional POWER-ATTRIBUTES-MIB module can be implemented to describe power attributes usage measurement in more detail ๐Ÿง It's aligned with the IEC 61850 7-2 standard for describing alternating current (AC) measurements.

The POWER-ATTRIBUTES-MIB module has a primary table, eoACPwrAttributesTable, which defines power attributes measurements for supported entPhysicalIndex entities. It's a sparse extension of the eoPowerTable, with entPhysicalIndex as the primary index ๐Ÿ—๏ธ This table holds info like the configuration (single phase, DEL 3 phases, or WYE 3 phases), frequency, power accuracy, total active, reactive, and apparent power, amperage, and voltage.

For three-phase power, there's an extra table with power attributes measurements per phase. It's double indexed by entPhysicalIndex and a phase index ๐Ÿ‘ฏ This table describes attributes specific to either WYE or DEL configurations.

In a DEL configuration, eoACPwrAttributesDelPhaseTable describes the phase-to-phase power attributes measurements, i.e., voltage. In a DEL configuration, the current is equal in all three phases โšก

In a WYE configuration, eoACPwrAttributesWyePhaseTable describes the phase-to-neutral power attributes measurements, i.e., voltage, current, active, reactive, and apparent power, and power factor ๐Ÿ’–

5.6. Optional Energy Measurement โšก

Okay so bestie, energy and demand numbers only mean something when they come from actual measurement hardware ๐Ÿ”Œ. If eoPowerMeasurementCaliber is unavailable, unknown, estimated, or presumed, then the energy and demand values are not useful ๐Ÿ’€.

Two tables handle energy measurement for an Energy Object: eoEnergyTable and eoEnergyParametersTable ๐Ÿงš. Energy and demand info can both be represented in eoEnergyTable, and demand information can be represented there too.

The eoEnergyParametersTable holds the settings that define the measurement:

  • eoEnergyParametersIndex, the index for the Energy Object ๐Ÿ”‘
  • eoEnergyObjectIndex, which is linked to the entPhysicalIndex of the Energy Object
  • eoEnergyParametersIntervalLength, the duration of the measurement intervals in seconds
  • eoEnergyParametersIntervalNumber, the number of successive intervals to be stored in eoEnergyTable
  • eoEnergyParametersIntervalMode, the type of measurement technique
  • eoEnergyParametersSampleRate, the sample rate used to calculate the average

Judicious choice of the sampling rate will ensure accurate measurement while not imposing an excessive polling burden ๐Ÿซถ.

There are three eoEnergyParametersIntervalMode types for energy measurement collection: period, sliding, and total ๐ŸŽ€. The three modes are based on IEC standard 61850-7-4 [IEC.61850-7-4]. Multiple eoEnergyParametersIntervalMode types MAY be configured simultaneously. For a given Energy Object, multiple modes (periodic, total, sliding window) of energy measurement collection can be configured with eoEnergyParametersIndex. Simultaneous measurement in multiple modes for a given Energy Object does depend on the Energy Object's capability, though ๐Ÿค“.

Here's how to read the three figures:

  • The horizontal axis is the current time. The symbol <--- L ---> stands for eoEnergyParametersIntervalLength, and S1, S2, S3, S4 are eoEnergyCollectionStartTime values (for eoEnergyParametersIntervalNumber intervals).
  • The vertical axis is the time interval of sampling. The value of eoEnergyConsumed can be obtained at the end of the sampling period, and =========== denotes the duration of the sampling period ๐Ÿ“Š.
      |             |             | =========== |
      |============ |             |             |
      |             |             |             |
      |             |============ |             |
      |             |             |             |
      | <--- L ---> | <--- L ---> | <--- L ---> |
      |             |             |             |
     S1            S2            S3             S4

     Figure 3: Period eoEnergyParametersIntervalMode

A eoEnergyParametersIntervalMode type of period specifies non-overlapping periodic measurements ๐Ÿ“…. That means the next eoEnergyCollectionStartTime is equal to the previous eoEnergyCollectionStartTime plus eoEnergyParametersIntervalLength, so S2=S1+L; S3=S2+L, ... โœจ.

               |============ |
               |             |
               | <--- L ---> |
               |             |
               |   |============ |
               |   |             |
               |   | <--- L ---> |
               |   |             |
               |   |   |============ |
               |   |   |             |
               |   |   | <--- L ---> |
               |   |   |             |
               |   |   |   |============ |
               |   |   |   |             |
               |   |   |   | <--- L ---> |
              S1   |   |   |             |
                   |   |   |             |
                   |   |   |             |
                  S2   |   |             |
                       |   |             |
                       |   |             |
                      S3   |             |
                           |             |
                           |             |
                          S4

       Figure 4: Sliding eoEnergyParametersIntervalMode

A eoEnergyParametersIntervalMode type of sliding specifies overlapping periodic measurements ๐ŸŒ€.

|                          |
|========================= |
|                          |
|                          |
|                          |
|  <--- Total length --->  |
|                          |
                 S1

Figure 5: Total eoEnergyParametersIntervalMode

A eoEnergyParametersIntervalMode type of total specifies a continuous measurement since the last reset ๐Ÿ”„. The value of eoEnergyParametersIntervalNumber should be (1) one, and eoEnergyParametersIntervalLength is ignored.

The eoEnergyParametersStatus is used to start and stop energy usage logging ๐Ÿšฆ. The status of this variable is "active" when all the objects in eoEnergyParametersTable are appropriate, and that in turn indicates whether or not eoEnergyTable entries exist. Last but not least, the eoEnergyParametersStorageType variable indicates the storage type for this row, meaning whether the persistence is maintained across a device reload ๐Ÿ’พ.

The eoEnergyTable is where the measurements live ๐Ÿ“. It holds eoEnergyConsumed, eoEnergyProvided, and eoEnergyStored, plus the unit scale of measured energy via eoEnergyUnitMultiplier, the percentage accuracy via eoEnergyAccuracy, and the maximum observed energy within a window in eoEnergyMaxConsumed, eoEnergyMaxProduced, and eoEnergyDiscontinuityTime.

Total energy consumed by an Energy Object can suffer from interruptions in the continuous measurement of energy consumption ๐Ÿ˜ญ. To show those interruptions, the object eoEnergyDiscontinuityTime is provided, which indicates the time of the last interruption of total energy measurement. eoEnergyDiscontinuityTime shall indicate the sysUpTime [RFC3418] when the device was reset.

Here's the example that puts it all together ๐Ÿง. First, to estimate energy, you need a time interval to sample energy. eoEnergyParametersIntervalLength can be set to "900 seconds" (15 minutes), and the number of consecutive intervals over which the maximum energy is calculated (eoEnergyParametersIntervalNumber) can be "10". The sampling rate internal to the Energy Object for measuring power usage (eoEnergyParametersSampleRate) can be "1000 milliseconds", as set by the Energy Object as a reasonable value. Then eoEnergyParametersStatus is set to active, which tells the Energy Object to start monitoring usage per the eoEnergyTable ๐Ÿซง.

The indices for eoEnergyTable are eoEnergyParametersIndex, which identifies the setting for the energy measurement collection of the Energy Object, and eoEnergyCollectionStartTime, which denotes the start time of the energy measurement interval based on sysUpTime [RFC3418] ๐Ÿ•ฐ๏ธ. The value of eoEnergyComsumed is the measured energy consumption over the time interval specified (eoEnergyParametersIntervalLength), based on the Energy Object's internal sampling rate (eoEnergyParametersSampleRate). When choosing values for eoEnergyParametersIntervalLength and eoEnergyParametersSampleRate, it is recommended to consider both the network element resources adequate to process and store the sample values and the mechanism used to calculate eoEnergyConsumed ๐Ÿง . The units are derived from eoEnergyUnitMultiplier. For example, if eoEnergyConsumed is "100" with eoEnergyUnitMultiplier equal to 0, the measured energy consumption of the Energy Object is 100 watt-hours โšก. The eoEnergyMaxConsumed is the maximum energy observed, which can be "150 watt-hours" ๐Ÿ’ช.

The eoEnergyTable has a buffer that retains a certain number of intervals, as defined by eoEnergyParametersIntervalNumber. If the default value of "10" is kept, the eoEnergyTable contains 10 energy measurements, including the maximum ๐Ÿ“š.

Here's a quick look at how the maximum energy gets calculated ๐Ÿ‘€. The first observed energy measurement is taken as the initial maximum. With each subsequent measurement, the maximum energy may be updated based on numerical comparison. The maximum value is retained for as long as measurements are taking place. Based on periodic polling of this table, an NMS could compute the maximum over a longer period, e.g., a month, 3 months, or a year ๐Ÿ“ˆ.


5.7. Fault Management ๐Ÿšจ

[RFC6988] specifies requirements about Power States, such as "the current Power State", "the time of the last state change", "the total time spent in each state", "the number of transitions to each state", and so on ๐Ÿ”‹. Some of these requirements are fulfilled explicitly by MIB objects such as eoPowerOperState, eoPowerStateTotalTime, and eoPowerStateEnterCount. The rest are met via the SNMP NOTIFICATION mechanism. The eoPowerStateChange SNMP notification is generated when the value of ePowerStateIndex, eoPowerOperState, or eoPowerAdminState has changed ๐Ÿ””.


6. Discovery ๐Ÿ”

It is probable that most Energy Objects will require the implementation of the ENERGY-OBJECT-CONTEXT-MIB [RFC7461] as a prerequisite for this MIB module ๐Ÿ’…. In that case, the eoPowerTable of the EMAN-ENERGY-OBJECT-MIB is cross-referenced with the eoTable of ENERGY-OBJECT-CONTEXT-MIB via entPhysicalIndex. Every Energy Object MUST implement entPhysicalIndex, entPhysicalClass, entPhysicalName, and entPhysicalUUID from the ENTITY-MIB [RFC6933]. entPhysicalIndex is the primary index for the Energy Object, and it characterizes the Energy Object in the ENERGY-OBJECT-MIB and the POWER-ATTRIBUTES-MIB MIB modules (this document) ๐Ÿฆ‹.

The NMS must first poll the ENERGY-OBJECT-CONTEXT-MIB MIB module [RFC7461], if it's available, to discover all the Energy Objects and the relationships between them ๐Ÿ—บ๏ธ. In the ENERGY-OBJECT-CONTEXT-MIB module tables, the Energy Objects are indexed by entPhysicalIndex.

From there, the NMS must poll the eoPowerStateTable (specified in the ENERGY-OBJECT-MIB module in this document), which enumerates, among other things, the maximum power usage ๐ŸŒˆ. The entries in the eoPowerStateTable are indexed by the Energy Object (entPhysicalIndex) and by the Power State Set (eoPowerStateIndex). So the maximum power usage is discovered per Energy Object, and the power usage per Power State of the Power State Set is discovered too. In other words, reading the eoPowerStateTable lets you discover each Power State within every Power State Set supported by the Energy Object ๐Ÿ‘‘.

The MIB module may be populated with Energy Object relationship information, which has its own Energy Object index value (entPhysicalIndex). However, the Energy Object relationship must be discovered via the ENERGY-OBJECT-CONTEXT-MIB module ๐Ÿงฉ.

Finally, the NMS can monitor the power attributes with the POWER-ATTRIBUTES-MIB MIB module, which reuses entPhysicalIndex to index the Energy Object ๐Ÿ“Š.


okay so [RFC6933] defines the ENTITY-MIB module, which lists the physical entities of a networking device (router, switch, etc.) and indexes those physical entities by entPhysicalIndex. bestie, from an energy-management standpoint, the physical entities that consume or produce energy are the ones we care about ๐Ÿ”Œ๐Ÿ’…

[RFC3433] defines the ENTITY-SENSOR MIB module, which gives us a standardized way to get info (the current value of the sensor, the operational status of the sensor, and the data-unit precision) from sensors built into networking devices ๐ŸŒธ Sensors are associated with each index of the entPhysicalIndex of the ENTITY-MIB [RFC6933]. The focus of the Monitoring and Control MIB for Power and Energy is measuring power usage of networking equipment indexed by the ENTITY-MIB, and lowkey this MIB also supports a customized power scale for power measurement, different Power States of networking equipment, and the functionality to configure those Power States ๐Ÿฆ‹

The Energy Objects are modeled by the entPhysicalIndex through the entPhysicalEntity MIB object specified in the eoTable in the ENERGY-OBJECT-CONTEXT-MIB MIB module [RFC7461] ๐Ÿงš

Okay, the ENTITY-SENSOR MIB [RFC3433] does not have the ANSI C12.x accuracy classes that electricity needs (e.g., 1%, 2%, and 0.5% accuracy classes). Indeed, entPhySensorPrecision [RFC3433] represents "The number of decimal places of precision in fixed-point sensor values returned by the associated entPhySensorValue object". ngl that's not it for power. The ANSI and IEC standards are used for power measurement, and these standards require an accuracy class, not the scientific-number precision model specified in RFC3433. That's where the eoPowerAccuracy MIB object comes in, since it models this accuracy ๐Ÿ’œ

Also, eoPowerUnitMultipler represents the scale factor per IEC 62053-21 [IEC.62053-21] and IEC 62053-22 [IEC.62053-22]. This is a more logical representation for power measurements than entPhySensorScale, with the mantissa and the exponent values X * 10 ^ Y ๐ŸŽ€

Power measurements that specify the qualifier 'UNITS' for each measured value in watts are used in the LLDP-EXT-MED-MIB, Power Ethernet [RFC3621], and UPS [RFC1628] MIBs. The same 'UNITS' qualifier is used for the power measurement values โœจ

Real talk, one cannot assume that the ENTITY-MIB and ENTITY-SENSOR MIBs are implemented for all Energy Objects that need to be monitored ๐Ÿ™ˆ A typical example is a converged building gateway, which can monitor other devices in a building and provides a proxy between SNMP and a protocol like BACnet. Another example is the home energy controller. In cases like these, the eoPhysicalEntity value contains the zero value, using the PhysicalIndexOrZero Textual Convention.

The eoPower is similar to entPhySensorValue [RFC3433], and the eoPowerUnitMultipler is similar to entPhySensorScale ๐Ÿ’–

For each entity in the ENTITY-MIB [RFC6933], the ENTITY-STATE MIB [RFC4268] specifies the operational states (entStateOper: unknown, enabled, disabled, testing), the alarm (entStateAlarm: unknown, underRepair, critical, major, minor, warning, indeterminate), and the possible values of standby states (entStateStandby: unknown, hotStandby, coldStandby, providingService) ๐ŸŒˆ

From a power-monitoring point of view, it's different from the entity operational states. Power States are required, as proposed in the Monitoring and Control MIB for Power and Energy ๐Ÿ”ฅ Those Power States can be mapped to the different operational states in the ENTITY-STATE MIB, if a formal mapping is required. For example, the entStateStandby "unknown", "hotStandby", and "coldStandby" states could map to the Power State "unknown", "ready", "standby", respectively, while the entStateStandby "providingService" could map to any "low" to "high" Power State โญ

The Power-over-Ethernet MIB [RFC3621] provides an energy monitoring and configuration framework for power over Ethernet devices. RFC 3621 defines a port group entity on a switch for power monitoring and management policy, and it does not use the entPhysicalIndex index. Indeed, pethMainPseConsumptionPower is indexed by the pethMainPseGroupIndex, which has no mapping with the entPhysicalIndex ๐Ÿฆ‹

If the Power-over-Ethernet MIB [RFC3621] is supported, the Energy Object eoethPortIndex and eoethPortGrpIndex contain the pethPsePortIndex and pethPsePortGroupIndex, respectively. However, one cannot assume that the Power-over-Ethernet MIB is implemented for most or all Energy Objects. In those cases, the eoethPortIndex and eoethPortGrpIndex values contain the zero value, via the new PethPsePortIndexOrZero and PethPsePortGroupIndexOrZero TCs ๐Ÿ“

In either case, the entPhysicalIndex MIB object is used as the unique Energy Object index ๐Ÿ’…

Note that, even though the Power-over-Ethernet MIB [RFC3621] was created after the ENTITY-SENSOR MIB [RFC3433], it does not reuse the precision notion from the ENTITY-SENSOR MIB, i.e., the entPhySensorPrecision MIB object. Plot twist ๐Ÿ˜ญ

To protect against unexpected power disruption, data centers and buildings make use of Uninterruptible Power Supplies (UPS) ๐Ÿ”‹ To protect critical assets, a UPS can be restricted to a particular subset or domain of the network. UPS usage typically lasts only for a finite period of time, until normal power supply is restored. Planning is required to decide on the capacity of the UPS based on output power and the duration of probable power outage. To properly provision UPS power in a data center or building, it's important to first understand the total demand required to support all the entities in the site. This demand can be assessed and monitored via the Monitoring and Control MIB for Power and Energy ๐Ÿ‘‘

The UPS MIB [RFC1628] provides information on the state of the UPS network. Implementing the UPS MIB is useful at the aggregate level of a data center or a building. The MIB module contains several groups of variables:

  • upsIdent: Identifies the UPS entity (name, model, etc.).
  • upsBattery group: Indicates the battery state (upsbatteryStatus, upsEstimatedMinutesRemaining, etc.)
  • upsInput group: Characterizes the input load to the UPS (number of input lines, voltage, current, etc.).
  • upsOutput: Characterizes the output from the UPS (number of output lines, voltage, current, etc.)
  • upsAlarms: Indicates the various alarm events.

The measurement of power in the UPS MIB is in volts, amperes, and watts. The units of power measurement are root mean square (RMS) volts and RMS amperes. They are not based on the EntitySensorDataScale and EntitySensorDataPrecision of ENTITY-SENSOR-MIB ๐Ÿซถ

Both the Monitoring and Control MIB for Power and Energy and the UPS MIB may be implemented on the same UPS SNMP agent, without conflict. In this case, the UPS device itself is the Energy Object, and any of the UPS meters or submeters are the Energy Objects, with a possible relationship as defined in [RFC7326] ๐ŸŒธ

The Link Layer Discovery Protocol (LLDP) is a Data Link Layer protocol used by network devices to advertise their identities, capabilities, and interconnections on a LAN network ๐Ÿ“ก

The Media Endpoint Discovery is an enhancement of LLDP, known as LLDP-MED. The LLDP-MED enhancements specifically address voice applications. LLDP-MED covers six basic areas: capability discovery, LAN speed and duplex discovery, network policy discovery, location identification discovery, inventory discovery, and power discovery ๐ŸŽ€

Of particular interest to the current MIB module is power discovery, which allows the endpoint device (such as a PoE phone) to convey power requirements to the switch. In power discovery, LLDP-MED has four Type-Length-Values (TLVs): power type, power source, power priority, and power value. Those TLVs provide information about the type of power (power sourcing entity versus powered device), how the device is powered (from the line, from a backup source, from external power source, etc.), the power priority (how important is it that this device has power?), and how much power the device needs. main character energy ๐Ÿ’œ

The power priority specified in the LLDP-MED MIB [LLDP-MED-MIB] actually comes from the Power-over-Ethernet MIB [RFC3621]. If the Power-over-Ethernet MIB [RFC3621] is supported, the exact value from the pethPsePortPowerPriority [RFC3621] is copied over into the lldpXMedRemXPoEPDPowerPriority [LLDP-MED-MIB]. Otherwise, the value in lldpXMedRemXPoEPDPowerPriority is "unknown". From the Monitoring and Control MIB for Power and Energy, it's possible to identify the pethPsePortPowerPriority [RFC3621] via the eoethPortIndex and eoethPortGrpIndex ๐Ÿงš

The lldpXMedLocXPoEPDPowerSource [LLDP-MED-MIB] is similar to eoPowerMeasurementLocal in indicating if the power for an attached device is local or from a remote device. If the LLDP-MED MIB is supported, the following mapping can be applied to eoPowerMeasurementLocal: lldpXMedLocXPoEPDPowerSource fromPSE(2) and local(3) can be mapped to false and true, respectively ๐ŸŒˆ

8. Structure of the MIB

The primary MIB object in the energyObjectMib MIB module is the energyObjectMibObjects root. The eoPowerTable table of energyObjectMibObjects describes the power measurement attributes of an Energy Object entity. The identity of a device in terms of uniquely identifying the Energy Object, and its relationship to other entities in the network, are addressed in [RFC7461] ๐Ÿฆ‹

Logically, this MIB module is a sparse extension of the ENERGY-OBJECT-CONTEXT-MIB module [RFC7461]. Thus, the following requirements that are applied to [RFC7461] are also applicable. As a requirement for this MIB module, [RFC7461] SHOULD be implemented, and as Module Compliance of ENTITY-MIB V4 [RFC6933] with respect to entity4CRCompliance MUST be supported. That requires four MIB objects: entPhysicalIndex, entPhysicalClass, entPhysicalName, and entPhysicalUUID MUST be implemented ๐Ÿ”ฅ

The eoMeterCapabilitiesTable is useful for enabling applications to determine the capabilities supported by the local management agent. This table indicates the energy-monitoring MIB groups that are supported by the local management system. By reading the value of this object, applications can know which tables contain the information and are usable, without walking through the table and querying every element, which would be a trial-and-error process ๐Ÿ“

The power measurement of an Energy Object contains information describing its power usage (eoPower) and its current Power State (eoPowerOperState). In addition to power usage, additional information is described: the units of measurement (eoPowerAccuracy, eoPowerUnitMultiplier), how the power usage measurement was obtained (eoPowerMeasurementCaliber), the source of the power measurement (eoPowerMeasurementLocal), and the type of power (eoPowerCurrentType) ๐Ÿ’–

An Energy Object may contain an optional eoEnergyTable to describe energy measurement information over time โญ

An Energy Object may contain an optional eoACPwrAttributesTable table (specified in the POWER-ATTRIBUTES-MIB module) that describes the electrical characteristics associated with the current Power State and usage โœจ

An Energy Object may also contain optional battery information associated with this entity ๐ŸŒธ

9. MIB Definitions โœจ

9.1. The IANAPowerStateSet-MIB Module โœจ

okay so this first one is the IANA-run MIB, and it's basically the official list of power state sets ๐Ÿ’… It only holds one Textual Convention, called PowerStateSet, which is the list of the power state sets and power state values an Energy Object can support. Here it is, exactly as published:

-- ************************************************************
--
--
-- This MIB, maintained by IANA, contains a single Textual
-- Convention: PowerStateSet
--
-- ************************************************************

IANAPowerStateSet-MIB DEFINITIONS ::= BEGIN

IMPORTS
    MODULE-IDENTITY, mib-2     FROM SNMPv2-SMI
    TEXTUAL-CONVENTION         FROM SNMPv2-TC;

ianaPowerStateSet MODULE-IDENTITY

    LAST-UPDATED "201502090000Z"    -- 9 February 2015
    ORGANIZATION "IANA"
    CONTACT-INFO "
                  Internet Assigned Numbers Authority
                  Postal: ICANN
                  12025 Waterfront Drive, Suite 300
                  Los Angeles, CA 90094
                  United States
                  Tel: +1-310-301 5800
                  EMail: iana@iana.org"

    DESCRIPTION
       "Copyright (c) 2015 IETF Trust and the persons identified as
        authors of the code.  All rights reserved.

        Redistribution and use in source and binary forms, with or
        without modification, is permitted pursuant to, and subject
        to the license terms contained in, the Simplified BSD License
        set forth in Section 4.c of the IETF Trust's Legal Provisions
        Relating to IETF Documents
        (http://trustee.ietf.org/license-info).

        This MIB module defines the PowerStateSet Textual
        Convention, which specifies the Power State Sets and
        Power State Set Values an Energy Object supports.

        The initial version of this MIB module was published in
        RFC 7460; for full legal notices see the RFC itself."

    -- revision history
    REVISION "201502090000Z"     -- 9 February 2015
    DESCRIPTION
        "Initial version of this MIB module, as published as RFC
        7460."

   ::= { mib-2 228 }

PowerStateSet ::= TEXTUAL-CONVENTION
    STATUS current
    DESCRIPTION
        "IANAPowerState is a textual convention that describes
        Power State Sets and Power State Set Values an Energy
        Object supports.  IANA has created a registry of Power
        State supported by an Energy Object and IANA shall
        administer the list of Power State Sets and Power
        States.

        The Textual Convention assumes that Power States in a
        Power State Set are limited to 255 distinct values.  For
        a Power State Set S, the named number with the value S *
        256 is allocated to indicate the Power State Set.  For a
        Power State X in the Power State Set S, the named number
        with the value S * 256 + X + 1 is allocated to represent
        the Power State.

        Requests for new values should be made to IANA via email
        (iana@iana.org)."
    REFERENCE
       "http://www.iana.org/assignments/power-state-sets"

    SYNTAX      INTEGER {
        other(0),        -- indicates other set
        unknown(255),    -- unknown

        ieee1621(256),    -- indicates IEEE1621 set
        ieee1621Off(257),
        ieee1621Sleep(258),
        ieee1621On(259),

        dmtf(512),        -- indicates DMTF set
        dmtfOn(513),
        dmtfSleepLight(514),
        dmtfSleepDeep(515),
        dmtfOffHard(516),
        dmtfOffSoft(517),
        dmtfHibernate(518),
        dmtfPowerOffSoft(519),
        dmtfPowerOffHard(520),
        dmtfMasterBusReset(521),
        dmtfDiagnosticInterrapt(522),
        dmtfOffSoftGraceful(523),
        dmtfOffHardGraceful(524),
        dmtfMasterBusResetGraceful(525),
        dmtfPowerCycleOffSoftGraceful(526),
        dmtfPowerCycleHardGraceful(527),

        eman(1024),       -- indicates EMAN set
        emanMechOff(1025),
        emanSoftOff(1026),
        emanHibernate(1027),
        emanSleep(1028),
        emanStandby(1029),
        emanReady(1030),
        emanLowMinus(1031),
        emanLow(1032),
        emanMediumMinus(1033),
        emanMedium(1034),
        emanHighMinus(1035),
        emanHigh(1036)
             }
END

9.2. The ENERGY-OBJECT-MIB MIB Module ๐Ÿ”Œ

next up is the big one, the ENERGY-OBJECT-MIB ๐Ÿคฉ this is the MIB you use to keep an eye on how much power network devices are pulling. The module header, the contact list, and the copyright notice all come first, and then the object definitions start. Here's the first chunk, verbatim:

-- ************************************************************
--
--
-- This MIB is used to monitor power usage of network
-- devices
--
-- *************************************************************

ENERGY-OBJECT-MIB DEFINITIONS ::= BEGIN

IMPORTS
    MODULE-IDENTITY,
    OBJECT-TYPE,
    NOTIFICATION-TYPE,
    mib-2,
    Integer32, Counter32, Unsigned32, TimeTicks
        FROM SNMPv2-SMI
    TEXTUAL-CONVENTION, RowStatus, TimeInterval,
    TimeStamp, TruthValue, StorageType
        FROM SNMPv2-TC
    MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
        FROM SNMPv2-CONF
    OwnerString
      FROM RMON-MIB
    entPhysicalIndex
       FROM ENTITY-MIB
    PowerStateSet
       FROM IANAPowerStateSet-MIB;

energyObjectMib MODULE-IDENTITY
    LAST-UPDATED    "201502090000Z"    -- 9 February 2015
    ORGANIZATION    "IETF EMAN Working Group"
    CONTACT-INFO
            "WG charter:
             http://datatracker.ietf.org/wg/eman/charter/

             Mailing Lists:
             General Discussion: eman@ietf.org
             To Subscribe:
             https://www.ietf.org/mailman/listinfo/eman

             Archive:
             http://www.ietf.org/mail-archive/web/eman

          Editors:
             Mouli Chandramouli
             Cisco Systems, Inc.
             Sarjapur Outer Ring Road
             Bangalore 560103
             India
             Phone: +91 80 4429 2409
             Email: moulchan@cisco.com

             Brad Schoening
             44 Rivers Edge Drive
             Little Silver, NJ 07739
             United States
             Email: brad.schoening@verizon.net

             Juergen Quittek
             NEC Europe, Ltd.
             NEC Laboratories Europe
             Network Research Division
             Kurfuersten-Anlage 36
             Heidelberg  69115
             Germany
             Phone: +49 6221 4342-115
             Email: quittek@neclab.eu

             Thomas Dietz
             NEC Europe, Ltd.
             NEC Laboratories Europe
             Network Research Division
             Kurfuersten-Anlage 36
             69115 Heidelberg
             Germany
             Phone: +49 6221 4342-128
             Email: Thomas.Dietz@nw.neclab.eu

             Benoit Claise
             Cisco Systems, Inc.
             De Kleetlaan 6a b1
             Degem 1831
             Belgium
             Phone:  +32 2 704 5622
             Email: bclaise@cisco.com"

    DESCRIPTION
       "Copyright (c) 2015 IETF Trust and the persons identified as
        authors of the code.  All rights reserved.

        Redistribution and use in source and binary forms, with or
        without modification, is permitted pursuant to, and subject
        to the license terms contained in, the Simplified BSD License
        set forth in Section 4.c of the IETF Trust's Legal Provisions
        Relating to IETF Documents
        (http://trustee.ietf.org/license-info).

        This MIB is used to monitor power and energy in
        devices.

        The tables eoMeterCapabilitiesTable and eoPowerTable
        are a sparse extension of the eoTable from the
        ENERGY-OBJECT-CONTEXT-MIB.  As a requirement,
        [RFC7461] SHOULD be implemented.

        Module Compliance of ENTITY-MIB v4 with respect to
        entity4CRCompliance MUST be supported which requires
        implementation of 4 MIB objects: entPhysicalIndex,
        entPhysicalClass, entPhysicalName and entPhysicalUUID."
    REVISION "201502090000Z"     -- 9 February 2015
    DESCRIPTION
       "Initial version, published as RFC 7460."

   ::= { mib-2 229 }

energyObjectMibNotifs OBJECT IDENTIFIER
    ::= { energyObjectMib 0 }

energyObjectMibObjects OBJECT IDENTIFIER
    ::= { energyObjectMib 1 }

energyObjectMibConform  OBJECT IDENTIFIER
    ::= { energyObjectMib 2 }

-- Textual Conventions

UnitMultiplier ::= TEXTUAL-CONVENTION
    STATUS           current
    DESCRIPTION
       "The Unit Multiplier is an integer value that represents
       the IEEE 61850 Annex A units multiplier associated with
       the integer units used to measure the power or energy.

       For example, when used with eoPowerUnitMultiplier, -3
       represents 10^-3 or milliwatts."
    REFERENCE
       "The International System of Units (SI), National
       Institute of Standards and Technology, Spec. Publ. 330,
       August 1991."
    SYNTAX INTEGER {
        yocto(-24),   -- 10^-24
        zepto(-21),   -- 10^-21
        atto(-18),    -- 10^-18
        femto(-15),   -- 10^-15
        pico(-12),    -- 10^-12
        nano(-9),     -- 10^-9
        micro(-6),    -- 10^-6
        milli(-3),    -- 10^-3
        units(0),     -- 10^0
        kilo(3),      -- 10^3
        mega(6),      -- 10^6
        giga(9),      -- 10^9
        tera(12),     -- 10^12
        peta(15),     -- 10^15
        exa(18),      -- 10^18
        zetta(21),    -- 10^21
        yotta(24)     -- 10^24
    }

-- Objects

eoMeterCapabilitiesTable OBJECT-TYPE
    SYNTAX          SEQUENCE OF EoMeterCapabilitiesEntry
    MAX-ACCESS      not-accessible
    STATUS          current
    DESCRIPTION
       "This table is useful for helping applications determine
       the monitoring capabilities supported by the local
       management agents.  It is possible for applications to
       know which tables are usable without going through a
       trial-and-error process."
    ::= { energyObjectMibObjects 1 }

eoMeterCapabilitiesEntry OBJECT-TYPE
    SYNTAX          EoMeterCapabilitiesEntry
    MAX-ACCESS      not-accessible
    STATUS          current
    DESCRIPTION
       "An entry describes the metering capability of an Energy
       Object."
    INDEX { entPhysicalIndex }
    ::= { eoMeterCapabilitiesTable  1 }

EoMeterCapabilitiesEntry ::= SEQUENCE {
          eoMeterCapability          BITS
               }

eoMeterCapability OBJECT-TYPE
    SYNTAX   BITS {
       none(0),
       powermetering(1),        -- power measurement
       energymetering(2),       -- energy measurement
       powerattributes(3)       -- power attributes
                   }
    MAX-ACCESS      read-only
    STATUS          current
    DESCRIPTION
       "An indication of the energy-monitoring capabilities
       supported by this agent.  This object use a BITS syntax
       and indicates the MIB groups supported by the probe.  By
       reading the value of this object, it is possible to
       determine the MIB tables supported."
    ::= { eoMeterCapabilitiesEntry 1  }

eoPowerTable OBJECT-TYPE
    SYNTAX          SEQUENCE OF EoPowerEntry
    MAX-ACCESS      not-accessible
    STATUS          current
    DESCRIPTION
       "This table lists Energy Objects."
    ::= { energyObjectMibObjects 2  }

eoPowerEntry OBJECT-TYPE
    SYNTAX          EoPowerEntry
    MAX-ACCESS      not-accessible
    STATUS          current
    DESCRIPTION
       "An entry describes the power usage of an Energy Object."
    INDEX { entPhysicalIndex }
    ::= { eoPowerTable  1 }

okay so this is where the energy object table gets really juicy ๐Ÿ’… every line below is copied exactly, because the MIB has to stay perfect ๐Ÿซถ

   EoPowerEntry ::= SEQUENCE {
       eoPower                         Integer32,
       eoPowerNameplate                Unsigned32,
       eoPowerUnitMultiplier           UnitMultiplier,
       eoPowerAccuracy                 Integer32,
       eoPowerMeasurementCaliber       INTEGER,
       eoPowerCurrentType             INTEGER,
       eoPowerMeasurementLocal         TruthValue,
       eoPowerAdminState               PowerStateSet,
       eoPowerOperState                PowerStateSet,
       eoPowerStateEnterReason         OwnerString
     }

   eoPower OBJECT-TYPE
       SYNTAX          Integer32
       UNITS          "watts"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates the power measured for the Energy
          Object.  For alternating current, this value is obtained
          as an average over fixed number of AC cycles.  This value
          is specified in SI units of watts with the magnitude of
          watts (milliwatts, kilowatts, etc.) indicated separately
          in eoPowerUnitMultiplier.  The accuracy of the measurement
          is specified in eoPowerAccuracy.  The direction of power
          flow is indicated by the sign on eoPower.  If the Energy
          Object is consuming power, the eoPower value will be
          positive.  If the Energy Object is producing power, the
          eoPower value will be negative.

          The eoPower MUST be less than or equal to the maximum
          power that can be consumed at the Power State specified
          by eoPowerState.

          The eoPowerMeasurementCaliber object specifies how the
          usage value reported by eoPower was obtained.  The eoPower
          value must report 0 if the eoPowerMeasurementCaliber is
          'unavailable'.  For devices that cannot measure or
          report power, this option can be used."
       ::= { eoPowerEntry 1 }

   eoPowerNameplate OBJECT-TYPE
       SYNTAX          Unsigned32
       UNITS          "watts"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates the rated maximum consumption for
          the fully populated Energy Object.  The nameplate power
          requirements are the maximum power numbers given in SI
          watts and, in almost all cases, are well above the
          expected operational consumption.  Nameplate power is
          widely used for power provisioning.  This value is
          specified in either units of watts or voltage and
          current.  The units are therefore SI watts or equivalent
          Volt-Amperes with the magnitude (milliwatts, kilowatts,
          etc.) indicated separately in eoPowerUnitMultiplier."
       ::= { eoPowerEntry 2 }

   eoPowerUnitMultiplier OBJECT-TYPE
       SYNTAX          UnitMultiplier
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "The magnitude of watts for the usage value in eoPower
          and eoPowerNameplate."
       ::= { eoPowerEntry 3 }

   eoPowerAccuracy OBJECT-TYPE
       SYNTAX          Integer32 (0..10000)
       UNITS           "hundredths of percent"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates a percentage value, in hundredths of a
          percent, representing the assumed accuracy of the usage
          reported by eoPower.  For example, the value 1010 means
          the reported usage is accurate to +/- 10.1 percent.  This
          value is zero if the accuracy is unknown or not
          applicable based upon the measurement method.

          ANSI and IEC define the following accuracy classes for
          power measurement:
               IEC 62053-22 60044-1 class 0.1, 0.2, 0.5, 1  3.
               ANSI C12.20 class 0.2, 0.5"
       ::= { eoPowerEntry 4 }

   eoPowerMeasurementCaliber   OBJECT-TYPE
       SYNTAX          INTEGER  {
                           unavailable(1) ,
                           unknown(2),
                           actual(3) ,
                           estimated(4),
                           static(5)                    }
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object specifies how the usage value reported by
          eoPower was obtained:

          - unavailable(1): Indicates that the usage is not
          available.  In such a case, the eoPower value must be 0
          for devices that cannot measure or report power this
          option can be used.

          - unknown(2): Indicates that the way the usage was
          determined is unknown.  In some cases, entities report
          aggregate power on behalf of another device.  In such
          cases it is not known whether the usage reported is
          actual, estimated, or static.

          - actual(3):  Indicates that the reported usage was
          measured by the entity through some hardware or direct
          physical means.  The usage data reported is not estimated
          or static but is the measured consumption rate.

          - estimated(4): Indicates that the usage was not
          determined by physical measurement.  The value is a
          derivation based upon the device type, state, and/or
          current utilization using some algorithm or heuristic.  It
          is presumed that the entity's state and current
          configuration were used to compute the value.

          - static(5): Indicates that the usage was not determined
          by physical measurement, algorithm, or derivation.  The
          usage was reported based upon external tables,
          specifications, and/or model information.  For example, a
          PC Model X draws 200W, while a PC Model Y draws 210W."
       ::= { eoPowerEntry 5 }

   eoPowerCurrentType OBJECT-TYPE
       SYNTAX      INTEGER  {
                          ac(1),
                          dc(2),
                          unknown(3)
                      }
       MAX-ACCESS  read-only
       STATUS      current
       DESCRIPTION
          "This object indicates whether the eoPower for the
          Energy Object reports alternating current 'ac', direct
          current 'dc', or that the current type is unknown."
       ::= { eoPowerEntry 6 }

   eoPowerMeasurementLocal  OBJECT-TYPE
       SYNTAX          TruthValue
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates the source of power measurement
          and can be useful when modeling the power usage of
          attached devices.  The power measurement can be performed
          by the entity itself or the power measurement of the
          entity can be reported by another trusted entity using a
          protocol extension.  A value of true indicates the
          measurement is performed by the entity, whereas false
          indicates that the measurement was performed by another
          entity."
       ::= { eoPowerEntry 7 }

   eoPowerAdminState OBJECT-TYPE
       SYNTAX          PowerStateSet
       MAX-ACCESS      read-write
       STATUS          current
       DESCRIPTION
          "This object specifies the desired Power State and the
          Power State Set for the Energy Object.  Note that other(0)
          is not a Power State Set and unknown(255) is not a Power
          State as such, but simply an indication that the Power
          State of the Energy Object is unknown.
          Possible values of eoPowerAdminState within the Power
          State Set are registered at IANA.
          A current list of assignments can be found at
          <http://www.iana.org/assignments/power-state-sets>"
       ::= { eoPowerEntry 8 }

   eoPowerOperState OBJECT-TYPE
       SYNTAX          PowerStateSet
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object specifies the current operational Power
          State and the Power State Set for the Energy Object.
          other(0) is not a Power State Set and unknown(255) is not
          a Power State as such, but simply an indication that the
          Power State of the Energy Object is unknown.

          Possible values of eoPowerOperState within the Power
          State Set are registered at IANA.  A current list of
          assignments can be found at
          <http://www.iana.org/assignments/power-state-sets>"
       ::= { eoPowerEntry 9 }

   eoPowerStateEnterReason OBJECT-TYPE
        SYNTAX         OwnerString
        MAX-ACCESS     read-write
        STATUS         current
        DESCRIPTION
          "This string object describes the reason for the
          eoPowerAdminState transition.  Alternatively, this string
          may contain with the entity that configured this Energy
          Object to this Power State."
        DEFVAL { "" }
        ::= { eoPowerEntry 10 }

   eoPowerStateTable OBJECT-TYPE
       SYNTAX          SEQUENCE OF EoPowerStateEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This table enumerates the maximum power usage, in watts,
          for every single supported Power State of each Energy
          Object.

          This table has cross-reference with the eoPowerTable,
          containing rows describing each Power State for the
          corresponding Energy Object.  For every Energy Object in
          the eoPowerTable, there is a corresponding entry in this
          table."
       ::= { energyObjectMibObjects 3  }

   eoPowerStateEntry OBJECT-TYPE
       SYNTAX          EoPowerStateEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "A eoPowerStateEntry extends a corresponding
          eoPowerEntry.  This entry displays max usage values at
          every single possible Power State supported by the Energy
          Object.
          For example, given the values of a Energy Object
          corresponding to a maximum usage of 0 W at the
          state emanmechoff, 8 W at state 6 (ready), 11 W at state
          emanmediumMinus, and 11 W at state emanhigh:

                  State      MaxUsage Units
               emanmechoff       0       W
               emansoftoff       0       W
               emanhibernate     0       W
               emansleep         0       W
               emanstandby       0       W
               emanready         8       W
               emanlowMinus      8       W
               emanlow          11       W
               emanmediumMinus  11       W
               emanmedium       11       W
               emanhighMinus    11       W
               emnanhigh        11       W

          Furthermore, this table also includes the total time in
          each Power State, along with the number of times a
          particular Power State was entered."

       INDEX { entPhysicalIndex, eoPowerStateIndex }
       ::= { eoPowerStateTable 1 }

   EoPowerStateEntry ::= SEQUENCE {
       eoPowerStateIndex              PowerStateSet,
       eoPowerStateMaxPower           Integer32,
       eoPowerStatePowerUnitMultiplier  UnitMultiplier,
       eoPowerStateTotalTime            TimeTicks,
       eoPowerStateEnterCount            Counter32
   }

   eoPowerStateIndex OBJECT-TYPE
       SYNTAX          PowerStateSet
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This object specifies the index of the Power State of
          the Energy Object within a Power State Set.  The semantics
          of the specific Power State can be obtained from the
          Power State Set definition."
       ::= { eoPowerStateEntry 1 }

okay bestie, the MIB keeps going and the energy tables are lowkey iconic ๐Ÿ’œ here's the rest of the module:

   eoPowerStateMaxPower OBJECT-TYPE
       SYNTAX          Integer32
       UNITS          "watts"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates the maximum power for the Energy
          Object at the particular Power State.  This value is
          specified in SI units of watts with the magnitude of the
          units (milliwatts, kilowatts, etc.) indicated separately
          in eoPowerStatePowerUnitMultiplier.  If the maximum power
          is not known for a certain Power State, then the value is
          encoded as 0xFFFFFFFF.

          For Power States not enumerated, the value of
          eoPowerStateMaxPower might be interpolated by using the
          next highest supported Power State."
       ::= { eoPowerStateEntry 2  }

   eoPowerStatePowerUnitMultiplier OBJECT-TYPE
       SYNTAX          UnitMultiplier
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "The magnitude of watts for the usage value in
          eoPowerStateMaxPower."
       ::= { eoPowerStateEntry 3  }

   eoPowerStateTotalTime OBJECT-TYPE
       SYNTAX      TimeTicks
       MAX-ACCESS  read-only
       STATUS      current
       DESCRIPTION
          "This object indicates the total time in hundredths
          of a second that the Energy Object has been in this power
          state since the last reset, as specified in the
          sysUpTime."
       ::= { eoPowerStateEntry 4  }

   eoPowerStateEnterCount OBJECT-TYPE
       SYNTAX       Counter32
       MAX-ACCESS   read-only
       STATUS       current
       DESCRIPTION
          "This object indicates how often the Energy Object has
          entered this power state, since the last reset of the
          device as specified in the sysUpTime."
       ::= { eoPowerStateEntry 5   }

   eoEnergyParametersTable OBJECT-TYPE
       SYNTAX          SEQUENCE OF EoEnergyParametersEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This table is used to configure the parameters for
          energy measurement collection in the table eoEnergyTable.
          This table allows the configuration of different
          measurement settings on the same Energy Object.
          Implementation of this table only makes sense for Energy
          Objects that an eoPowerMeasurementCaliber of actual."
       ::= { energyObjectMibObjects 4   }

   eoEnergyParametersEntry OBJECT-TYPE
       SYNTAX          EoEnergyParametersEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "An entry controls an energy measurement in
          eoEnergyTable."
       INDEX { entPhysicalIndex, eoEnergyParametersIndex }
       ::= { eoEnergyParametersTable 1 }

   EoEnergyParametersEntry ::= SEQUENCE {
       eoEnergyParametersIndex            Integer32,
       eoEnergyParametersIntervalLength   TimeInterval,
       eoEnergyParametersIntervalNumber   Unsigned32,
       eoEnergyParametersIntervalMode     INTEGER,
       eoEnergyParametersIntervalWindow   TimeInterval,
       eoEnergyParametersSampleRate       Unsigned32,
       eoEnergyParametersStorageType      StorageType,
       eoEnergyParametersStatus           RowStatus
                                }

   eoEnergyParametersIndex OBJECT-TYPE
       SYNTAX           Integer32 (1..2147483647)
       MAX-ACCESS       not-accessible
       STATUS           current
       DESCRIPTION
          "This object specifies the index of the Energy Parameters
          setting for collection of energy measurements for an
          Energy Object.  An Energy Object can have multiple
          eoEnergyParametersIndex, depending on the capabilities of
          the Energy Object"
       ::= { eoEnergyParametersEntry 2 }

   eoEnergyParametersIntervalLength OBJECT-TYPE
       SYNTAX          TimeInterval
       MAX-ACCESS      read-create
       STATUS          current
       DESCRIPTION
          "This object indicates the length of time in hundredths
          of a second over which to compute the average
          eoEnergyConsumed measurement in the eoEnergyTable table.
          The computation is based on the Energy Object's internal
          sampling rate of power consumed or produced by the Energy
          Object.  The sampling rate is the rate at which the Energy
          Object can read the power usage and may differ based on
          device capabilities.  The average energy consumption is
          then computed over the length of the interval.  The
          default value of 15 minutes is a common interval used in
          industry."
       DEFVAL { 90000 }
       ::= { eoEnergyParametersEntry 3 }

   eoEnergyParametersIntervalNumber OBJECT-TYPE
       SYNTAX          Unsigned32
       MAX-ACCESS      read-create
       STATUS          current
       DESCRIPTION
          "The number of intervals maintained in the eoEnergyTable.
          Each interval is characterized by a specific
          eoEnergyCollectionStartTime, used as an index to the
          table eoEnergyTable.  Whenever the maximum number of
          entries is reached, the measurement over the new interval
          replaces the oldest measurement.  There is one exception
          to this rule: when the eoEnergyMaxConsumed and/or
          eoEnergyMaxProduced are in (one of) the two oldest
          measurement(s), they are left untouched and the next
          oldest measurement is replaced."
          DEFVAL { 10 }
       ::= { eoEnergyParametersEntry 4 }

   eoEnergyParametersIntervalMode OBJECT-TYPE
     SYNTAX          INTEGER  {
                         period(1),
                         sliding(2),
                         total(3)
                     }
     MAX-ACCESS      read-create
     STATUS          current
     DESCRIPTION
          "A control object to define the mode of interval
          calculation for the computation of the average
          eoEnergyConsumed or eoEnergyProvided measurement in the
          eoEnergyTable table.

          A mode of period(1) specifies non-overlapping periodic
          measurements.

          A mode of sliding(2) specifies overlapping sliding
          windows where the interval between the start of one
          interval and the next is defined in
          eoEnergyParametersIntervalWindow.

          A mode of total(3) specifies non-periodic measurement.
          In this mode only one interval is used as this is a
          continuous measurement since the last reset.  The value of
          eoEnergyParametersIntervalNumber should be (1) one and
          eoEnergyParametersIntervalLength is ignored."
      ::= { eoEnergyParametersEntry 5 }

   eoEnergyParametersIntervalWindow OBJECT-TYPE
       SYNTAX          TimeInterval
       MAX-ACCESS      read-create
       STATUS          current
       DESCRIPTION
          "The length of the duration window between the starting
          time of one sliding window and the next starting time in
          hundredths of seconds, used to compute the average of
          eoEnergyConsumed, eoEnergyProvided measurements in the
          eoEnergyTable table.  This is valid only when the
          eoEnergyParametersIntervalMode is sliding(2).  The
          eoEnergyParametersIntervalWindow value should be a
          multiple of eoEnergyParametersSampleRate."
       ::= { eoEnergyParametersEntry 6 }

   eoEnergyParametersSampleRate OBJECT-TYPE
       SYNTAX          Unsigned32
      UNITS           "Milliseconds"
       MAX-ACCESS      read-create
       STATUS          current
       DESCRIPTION
          "The sampling rate, in milliseconds, at which the Energy
          Object should poll power usage in order to compute the
          average eoEnergyConsumed, eoEnergyProvided measurements
          in the table eoEnergyTable.  The Energy Object should
          initially set this sampling rate to a reasonable value,
          i.e., a compromise between intervals that will provide
          good accuracy by not being too long, but not so short
          that they affect the Energy Object performance by
          requesting continuous polling.  If the sampling rate is
          unknown, the value 0 is reported.  The sampling rate
          should be selected so that
          eoEnergyParametersIntervalWindow is a multiple of
          eoEnergyParametersSampleRate.  The default value is one
          second."
       DEFVAL { 1000 }
       ::= { eoEnergyParametersEntry 7 }

   eoEnergyParametersStorageType OBJECT-TYPE
       SYNTAX          StorageType
       MAX-ACCESS      read-create
       STATUS          current
       DESCRIPTION
           "This variable indicates the storage type for this row."
       DEFVAL { nonVolatile }
       ::= {eoEnergyParametersEntry 8 }

   eoEnergyParametersStatus OBJECT-TYPE
       SYNTAX          RowStatus
       MAX-ACCESS      read-create
       STATUS          current
       DESCRIPTION
          "The status of this row.  The eoEnergyParametersStatus is
          used to start or stop energy usage logging.  An entry
          status may not be active(1) unless all objects in the
          entry have an appropriate value.  If this object is not
          equal to active, all associated usage-data logged into
          the eoEnergyTable will be deleted.  The data can be
          destroyed by setting up the eoEnergyParametersStatus to
          destroy."
       ::= {eoEnergyParametersEntry 9 }

   eoEnergyTable OBJECT-TYPE
       SYNTAX          SEQUENCE OF EoEnergyEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This table lists Energy Object energy measurements.
          Entries in this table are only created if the
          corresponding value of object eoPowerMeasurementCaliber
          is active(3), i.e., if the power is actually metered."
       ::= { energyObjectMibObjects 5   }

   eoEnergyEntry OBJECT-TYPE
       SYNTAX          EoEnergyEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
           "An entry describing energy measurements."
       INDEX { eoEnergyParametersIndex,
               eoEnergyCollectionStartTime }
       ::= { eoEnergyTable 1 }

   EoEnergyEntry ::= SEQUENCE {
       eoEnergyCollectionStartTime       TimeTicks,
        eoEnergyConsumed                  Unsigned32,
        eoEnergyProvided                  Unsigned32,
        eoEnergyStored                    Unsigned32,
        eoEnergyUnitMultiplier            UnitMultiplier,
        eoEnergyAccuracy                  Integer32,
        eoEnergyMaxConsumed               Unsigned32,
        eoEnergyMaxProduced               Unsigned32,
        eoEnergyDiscontinuityTime         TimeStamp
        }

   eoEnergyCollectionStartTime OBJECT-TYPE
       SYNTAX          TimeTicks
       UNITS          "hundredths of a second"
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "The time (in hundredths of a second) since the
          network management portion of the system was last
          re-initialized, as specified in the sysUpTime RFC 3418.
          This object specifies the start time of the energy
          measurement sample."
       REFERENCE
         "RFC 3418: Management Information Base (MIB) for the
          Simple Network Management Protocol (SNMP)"
       ::= { eoEnergyEntry 1 }

eoEnergyConsumed, eoEnergyProvided, and friends are giving full energy-tracking girlboss ๐Ÿ”‹๐Ÿ’… Watt-hours everywhere, and the multiplier object tells you whether you're looking at Wh, kWh, or MWh ๐Ÿงฎ

   eoEnergyConsumed OBJECT-TYPE
       SYNTAX          Unsigned32
       UNITS           "Watt-hours"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates the energy consumed in units of
          watt-hours for the Energy Object over the defined
          interval.  This value is specified in the common billing
          units of watt-hours with the magnitude of watt-hours
          kWh, MWh, etc.) indicated separately in
          eoEnergyUnitMultiplier."
       ::= { eoEnergyEntry 2 }

   eoEnergyProvided OBJECT-TYPE
       SYNTAX          Unsigned32
       UNITS           "Watt-hours"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates the energy produced in units of
          watt-hours for the Energy Object over the defined
          interval.

          This value is specified in the common billing units of
          watt-hours with the magnitude of watt-hours (kWh, MWh,
          etc.) indicated separately in
          eoEnergyUnitMultiplier."
       ::= { eoEnergyEntry 3 }

   eoEnergyStored OBJECT-TYPE
       SYNTAX          Unsigned32
       UNITS           "Watt-hours"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates the difference of the energy
          consumed and energy produced for an Energy Object in
          units of watt-hours for the Energy Object over the
          defined interval.  This value is specified in the common
          billing units of watt-hours with the magnitude of
          watt-hours (kWh, MWh, etc.) indicated separately in
          eoEnergyUnitMultiplier."
       ::= { eoEnergyEntry 4 }

   eoEnergyUnitMultiplier OBJECT-TYPE
       SYNTAX          UnitMultiplier
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object is the magnitude of watt-hours for the
          energy field in eoEnergyConsumed, eoEnergyProvided,
          eoEnergyStored, eoEnergyMaxConsumed, and
          eoEnergyMaxProduced."
       ::= { eoEnergyEntry 5  }

   eoEnergyAccuracy OBJECT-TYPE
       SYNTAX          Integer32 (0..10000)
       UNITS           "hundredths of percent"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates a percentage accuracy, in hundredths
          of a percent, of Energy usage reporting.  eoEnergyAccuracy
          is applicable to all Energy measurements in the
          eoEnergyTable.

          For example, 1010 means the reported usage is accurate to
          +/- 10.1 percent.

          This value is zero if the accuracy is unknown."
       ::= { eoEnergyEntry 6 }

   eoEnergyMaxConsumed OBJECT-TYPE
       SYNTAX          Unsigned32
       UNITS          "Watt-hours"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object is the maximum energy observed in
          eoEnergyConsumed since the monitoring started or was
          reinitialized.  This value is specified in the common
          billing units of watt-hours with the magnitude of
          watt-hours (kWh, MWh, etc.) indicated separately in
          eoEnergyUnitMultiplier."
       ::= { eoEnergyEntry 7  }

   eoEnergyMaxProduced OBJECT-TYPE
       SYNTAX          Unsigned32
       UNITS          "Watt-hours"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object is the maximum energy ever observed in
          eoEnergyEnergyProduced since the monitoring started.  This
          value is specified in the units of watt-hours with the
          magnitude of watt-hours (kWh, MWh, etc.) indicated
          separately in eoEnergyEnergyUnitMultiplier."
       ::= { eoEnergyEntry 8 }

    eoEnergyDiscontinuityTime OBJECT-TYPE
       SYNTAX       TimeStamp
       MAX-ACCESS  read-only
       STATUS      current
       DESCRIPTION
          "The value of sysUpTime RFC 3418 on the most recent
          occasion at which any one or more of this entity's energy
          counters in this table suffered a discontinuity:
          eoEnergyConsumed, eoEnergyProvided or eoEnergyStored.  If
          no such discontinuities have occurred since the last
          re-initialization of the local management subsystem, then
          this object contains a zero value."
       REFERENCE
          "RFC 3418: Management Information Base (MIB) for the
           Simple Network Management Protocol (SNMP)"
       ::= { eoEnergyEntry 9 }

Okay, now the notifications ๐Ÿ”” this is where the MIB starts talking back to you ๐Ÿซถ

   -- Notifications

   eoPowerEnableStatusNotification
   OBJECT-TYPE
       SYNTAX          TruthValue
       MAX-ACCESS      read-write
       STATUS          current
       DESCRIPTION
          "This object controls whether the system produces
          notifications for eoPowerStateChange.  A false value will
          prevent these notifications from being generated."
       DEFVAL { false }
       ::= { energyObjectMibNotifs 1 }

   eoPowerStateChange NOTIFICATION-TYPE
       OBJECTS       {eoPowerAdminState, eoPowerOperState,
   eoPowerStateEnterReason}
       STATUS        current
       DESCRIPTION
          "The SNMP entity generates the eoPowerStateChange when
          the values of eoPowerAdminState or eoPowerOperState,
          in the context of the Power State Set, have changed for
          the Energy Object represented by the entPhysicalIndex."
       ::= { energyObjectMibNotifs 2 }

Conformance time, bestie ๐ŸŽ€ This is the part where we decide who gets the full compliance crown ๐Ÿ‘‘

   -- Conformance

   energyObjectMibCompliances  OBJECT IDENTIFIER
       ::= { energyObjectMibConform 1 }

   energyObjectMibGroups  OBJECT IDENTIFIER
       ::= { energyObjectMibConform 2 }
   energyObjectMibFullCompliance MODULE-COMPLIANCE
       STATUS          current
       DESCRIPTION
          "When this MIB is implemented with support for
          read-create, then such an implementation can
          claim full compliance.  Such devices can then
          be both monitored and configured with this MIB.

          Module Compliance of RFC 6933
          with respect to entity4CRCompliance MUST
          be supported, which requires implementation
          of four MIB objects: entPhysicalIndex, entPhysicalClass,
          entPhysicalName and entPhysicalUUID."
       REFERENCE
          "RFC 6933: Entity MIB (Version 4)"
       MODULE          -- this module
       MANDATORY-GROUPS {
                   energyObjectMibTableGroup,
                   energyObjectMibStateTableGroup,
                   eoPowerEnableStatusNotificationGroup,
                   energyObjectMibNotifGroup
                       }

       GROUP     energyObjectMibEnergyTableGroup
          DESCRIPTION
             "A compliant implementation does not
              have to implement."

       GROUP    energyObjectMibEnergyParametersTableGroup
          DESCRIPTION
              "A compliant implementation does not
               have to implement."

       GROUP     energyObjectMibMeterCapabilitiesTableGroup
          DESCRIPTION
              "A compliant implementation does not
               have to implement."
       ::= { energyObjectMibCompliances 1 }

   energyObjectMibReadOnlyCompliance MODULE-COMPLIANCE
       STATUS          current
       DESCRIPTION
          "When this MIB is implemented without support for
          read-create (i.e., in read-only mode), then such an
          implementation can claim read-only compliance.  Such a
          device can then be monitored but cannot be
          configured with this MIB.

          Module Compliance of [RFC6933] with respect to
          entity4CRCompliance MUST be supported which requires
          implementation of 4 MIB objects: entPhysicalIndex,
          entPhysicalClass, entPhysicalName and entPhysicalUUID."
       REFERENCE
          "RFC 6933: Entity MIB (Version 4)"
       MODULE          -- this module
       MANDATORY-GROUPS {
                           energyObjectMibTableGroup,
                           energyObjectMibStateTableGroup,
                           energyObjectMibNotifGroup
                         }

       ::= { energyObjectMibCompliances 2 }

Last stretch of this part: the Units of Conformance groups ๐Ÿงฉ each group is just a bundle of objects, so these are the little packs you sign up for ๐Ÿ“

   -- Units of Conformance

   energyObjectMibTableGroup OBJECT-GROUP
      OBJECTS         {
                           eoPower,
                           eoPowerNameplate,
                           eoPowerUnitMultiplier,
                           eoPowerAccuracy,
                           eoPowerMeasurementCaliber,
                           eoPowerCurrentType,
                           eoPowerMeasurementLocal,
                           eoPowerAdminState,
                           eoPowerOperState,
                           eoPowerStateEnterReason
                       }
      STATUS          current
      DESCRIPTION
          "This group contains the collection of all the objects
          related to the Energy Object."
      ::= { energyObjectMibGroups 1 }

   energyObjectMibStateTableGroup OBJECT-GROUP
       OBJECTS      {
                            eoPowerStateMaxPower,
                            eoPowerStatePowerUnitMultiplier,
                            eoPowerStateTotalTime,
                            eoPowerStateEnterCount
                       }
       STATUS          current
       DESCRIPTION
          "This group contains the collection of all the objects
          related to the Power State."
       ::= { energyObjectMibGroups 2 }

   energyObjectMibEnergyParametersTableGroup OBJECT-GROUP
       OBJECTS         {
                           eoEnergyParametersIntervalLength,
                           eoEnergyParametersIntervalNumber,
                           eoEnergyParametersIntervalMode,
                           eoEnergyParametersIntervalWindow,
                           eoEnergyParametersSampleRate,
                           eoEnergyParametersStorageType,
                           eoEnergyParametersStatus
                       }
       STATUS          current
       DESCRIPTION
           "This group contains the collection of all the objects
           related to the configuration of the Energy Table."
       ::= { energyObjectMibGroups 3 }

   energyObjectMibEnergyTableGroup OBJECT-GROUP
       OBJECTS         {
                        -- Note that object
                      -- eoEnergyCollectionStartTime is not
                           -- included since it is not-accessible
                           eoEnergyConsumed,
                           eoEnergyProvided,
                           eoEnergyStored,
                           eoEnergyUnitMultiplier,
                           eoEnergyAccuracy,
                           eoEnergyMaxConsumed,
                           eoEnergyMaxProduced,
                           eoEnergyDiscontinuityTime
                       }
       STATUS          current
       DESCRIPTION
           "This group contains the collection of all the objects
           related to the Energy Table."
       ::= { energyObjectMibGroups 4 }

   energyObjectMibMeterCapabilitiesTableGroup OBJECT-GROUP
       OBJECTS         {
                            eoMeterCapability
                       }
       STATUS          current
       DESCRIPTION
          "This group contains the object indicating the capability
          of the Energy Object"
       ::= { energyObjectMibGroups 5 }

   eoPowerEnableStatusNotificationGroup OBJECT-GROUP
       OBJECTS         { eoPowerEnableStatusNotification  }
       STATUS          current
       DESCRIPTION
          "The collection of objects that are used to enable
          notification."
       ::= { energyObjectMibGroups 6 }

Next up, we keep going with the rest of the MIB ๐Ÿฆ‹ the plot is thickening โœจ

   energyObjectMibNotifGroup NOTIFICATION-GROUP
       NOTIFICATIONS    {
                           eoPowerStateChange
                       }
       STATUS          current
       DESCRIPTION
          "This group contains the notifications for
          the Monitoring and Control MIB for Power and Energy."
       ::= { energyObjectMibGroups 7 }

   END

9.3. The POWER-ATTRIBUTES-MIB MIB Module โœจ

okay bestie, this is the POWER-ATTRIBUTES-MIB and it's basically the AC power glow-up ๐Ÿ’… it's all about monitoring power attributes on networked devices, and the header literally says it's an extension of the energyObjectMib module ๐ŸŽ€ the table is a sparse augmentation of eoPowerTable, so it only fills in the AC stuff ๐Ÿฆ‹ the DESCRIPTION also covers both three-phase and single-phase setups, which is so thorough of them ๐Ÿ˜ญ

   -- ************************************************************
   --
   -- This MIB module is used to monitor power attributes of
   -- networked devices with measurements.
   --
   -- This MIB module is an extension of energyObjectMib module.
   --
   -- *************************************************************

   POWER-ATTRIBUTES-MIB DEFINITIONS ::= BEGIN

   IMPORTS
       MODULE-IDENTITY,
       OBJECT-TYPE,
       mib-2,
       Integer32, Unsigned32
          FROM SNMPv2-SMI
       MODULE-COMPLIANCE,
       OBJECT-GROUP
           FROM SNMPv2-CONF
      UnitMultiplier
         FROM ENERGY-OBJECT-MIB
       entPhysicalIndex
          FROM ENTITY-MIB;

   powerAttributesMIB MODULE-IDENTITY
       LAST-UPDATED    "201502090000Z"    -- 9 February 2015
       ORGANIZATION    "IETF EMAN Working Group"
       CONTACT-INFO
               "WG charter:
                http://datatracker.ietf.org/wg/eman/charter/

                Mailing Lists:
                General Discussion: eman@ietf.org

                To Subscribe:
                https://www.ietf.org/mailman/listinfo/eman

                Archive:
                http://www.ietf.org/mail-archive/web/eman

             Editors:

                Mouli Chandramouli
                Cisco Systems, Inc.
                Sarjapur Outer Ring Road
                Bangalore 560103
                India
                Phone: +91 80 4429 2409
                Email: moulchan@cisco.com

                Brad Schoening
                44 Rivers Edge Drive
                Little Silver, NJ 07739
                United States
                Email: brad.schoening@verizon.net

                Juergen Quittek
                NEC Europe Ltd.
                NEC Laboratories Europe
                Network Research Division
                Kurfuersten-Anlage 36
                Heidelberg  69115
                Germany
                Phone: +49 6221 4342-115
                Email: quittek@neclab.eu

                Thomas Dietz
                NEC Europe Ltd.
                NEC Laboratories Europe
                Network Research Division
                Kurfuersten-Anlage 36
                69115 Heidelberg
                Germany
                Phone: +49 6221 4342-128
                Email: Thomas.Dietz@nw.neclab.eu

                Benoit Claise
                Cisco Systems, Inc.
                De Kleetlaan 6a b1
                Degem 1831
                Belgium
                Phone:  +32 2 704 5622
                Email: bclaise@cisco.com"

       DESCRIPTION
          "Copyright (c) 2015 IETF Trust and the persons identified as
           authors of the code.  All rights reserved.

           Redistribution and use in source and binary forms, with or
           without modification, is permitted pursuant to, and subject
           to the license terms contained in, the Simplified BSD License
           set forth in Section 4.c of the IETF Trust's Legal Provisions
           Relating to IETF Documents
           (http://trustee.ietf.org/license-info).

           This MIB is used to report AC power attributes in devices.
           The table is a sparse augmentation of the eoPowerTable table
           from the energyObjectMib module.  Both three-phase and
           single-phase power configurations are supported.

           As a requirement for this MIB module, RFC 7461 SHOULD be
           implemented.

           Module Compliance of ENTITY-MIB v4 with respect to
           entity4CRCompliance MUST be supported which requires
           implementation of four MIB objects: entPhysicalIndex,
           entPhysicalClass, entPhysicalName, and entPhysicalUUID."
       REVISION "201502090000Z"     -- 9 February 2015
       DESCRIPTION
          "Initial version, published as RFC 7460"

      ::= { mib-2 230 }

   powerAttributesMIBConform  OBJECT IDENTIFIER
       ::= { powerAttributesMIB 0 }

   powerAttributesMIBObjects OBJECT IDENTIFIER
       ::= { powerAttributesMIB 1 }

   -- Objects

   eoACPwrAttributesTable OBJECT-TYPE
       SYNTAX          SEQUENCE OF EoACPwrAttributesEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This table contains power attributes measurements for
          supported entPhysicalIndex entities.  It is a sparse
          extension of the eoPowerTable."
       ::= { powerAttributesMIBObjects 1 }

   eoACPwrAttributesEntry OBJECT-TYPE

       SYNTAX          EoACPwrAttributesEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This is a sparse extension of the eoPowerTable with
          entries for power attributes measurements or
          configuration.  Each measured value corresponds to an
          attribute in IEC 61850-7-4 for non-phase measurements
          within the object MMXN."
       INDEX { entPhysicalIndex }
       ::= { eoACPwrAttributesTable 1 }

   EoACPwrAttributesEntry ::= SEQUENCE {
       eoACPwrAttributesConfiguration      INTEGER,
       eoACPwrAttributesAvgVoltage          Integer32,
       eoACPwrAttributesAvgCurrent          Unsigned32,
       eoACPwrAttributesFrequency           Integer32,
       eoACPwrAttributesPowerUnitMultiplier UnitMultiplier,
       eoACPwrAttributesPowerAccuracy      Integer32,
       eoACPwrAttributesTotalActivePower    Integer32,
       eoACPwrAttributesTotalReactivePower  Integer32,
       eoACPwrAttributesTotalApparentPower  Integer32,
       eoACPwrAttributesTotalPowerFactor    Integer32,
       eoACPwrAttributesThdCurrent          Integer32,
       eoACPwrAttributesThdVoltage         Integer32
                             }

   eoACPwrAttributesConfiguration OBJECT-TYPE
       SYNTAX INTEGER {
               sngl(1),
               del(2),
               wye(3)
             }
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "Configuration describes the physical configurations of
          the power supply lines:

             * alternating current, single phase (SNGL)
             * alternating current, three-phase delta (DEL)
             * alternating current, three-phase Y (WYE)

          Three-phase configurations can be either connected in a
          triangular delta (DEL) or star Y (WYE) system.  WYE
          systems have a shared neutral voltage, while DEL systems
          do not.  Each phase is offset 120 degrees to each other."
       ::= { eoACPwrAttributesEntry 1 }

   eoACPwrAttributesAvgVoltage OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "0.1 Volt AC"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value for average of the voltage measured
          over an integral number of AC cycles.  For a three-phase
          system, this is the average voltage (V1+V2+V3)/3.  IEC
          61850-7-4 measured value attribute 'Vol'."
       ::= { eoACPwrAttributesEntry 2 }

   eoACPwrAttributesAvgCurrent OBJECT-TYPE
       SYNTAX          Unsigned32
       UNITS           "amperes"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value for average of the current measured
          over an integral number of AC cycles.  For a three-phase
          system, this is the average current (I1+I2+I3)/3.  IEC
          61850-7-4 attribute 'Amp'."
       ::= { eoACPwrAttributesEntry 3 }

   eoACPwrAttributesFrequency OBJECT-TYPE
       SYNTAX          Integer32 (4500..6500)
       UNITS           "0.01 hertz"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value for the basic frequency of the AC
          circuit.  IEC 61850-7-4 attribute 'Hz'."
       ::= { eoACPwrAttributesEntry 4 }

   eoACPwrAttributesPowerUnitMultiplier OBJECT-TYPE
       SYNTAX          UnitMultiplier
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "The magnitude of watts for the usage value in
          eoACPwrAttributesTotalActivePower,
          eoACPwrAttributesTotalReactivePower,
          and eoACPwrAttributesTotalApparentPower measurements.
          For three-phase power systems, this will also include
          eoACPwrAttributesWyeActivePower,
          eoACPwrAttributesWyeReactivePower, and
          eoACPwrAttributesWyeApparentPower."
       ::= { eoACPwrAttributesEntry 5 }

   eoACPwrAttributesPowerAccuracy OBJECT-TYPE
       SYNTAX          Integer32 (0..10000)
       UNITS           "hundredths of percent"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "This object indicates a percentage value, in hundredths of a
          percent, representing the presumed accuracy of active,
          reactive, and apparent power usage reporting.  For
          example, 1010 means the reported usage is accurate to +/-
          10.1 percent.  This value is zero if the accuracy is
          unknown.

          ANSI and IEC define the following accuracy classes for
          power measurement: IEC 62053-22 & 60044-1 class 0.1, 0.2,
          0.5, 1, & 3.
          ANSI C12.20 class 0.2 & 0.5"
       ::= { eoACPwrAttributesEntry 6 }

   eoACPwrAttributesTotalActivePower OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "watts"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value of the actual power delivered to or
          consumed by the load.  IEC 61850-7-4 attribute 'TotW'."
       ::= { eoACPwrAttributesEntry 7 }

   eoACPwrAttributesTotalReactivePower OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "volt-amperes reactive"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value of the reactive portion of the apparent
          power.  IEC 61850-7-4 attribute 'TotVAr'."
       ::= { eoACPwrAttributesEntry 8 }

   eoACPwrAttributesTotalApparentPower OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "volt-amperes"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value of the voltage and current that
          determines the apparent power.  The apparent power is the
          vector sum of real and reactive power.

          Note: watts and volt-amperes are equivalent units and may
          be combined.  IEC 61850-7-4 attribute 'TotVA'."
       ::= { eoACPwrAttributesEntry 9 }

   eoACPwrAttributesTotalPowerFactor OBJECT-TYPE
       SYNTAX          Integer32 (-10000..10000)
       UNITS           "hundredths"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value ratio of the real power flowing to the
          load versus the apparent power.  It is dimensionless and
          expressed here as a percentage value in hundredths.  A power
          factor of 100% indicates there is no inductance load and
          thus no reactive power.  A Power Factor can be positive or
          negative, where the sign should be in lead/lag (IEEE)
          form.  IEC 61850-7-4 attribute 'TotPF'."
       ::= { eoACPwrAttributesEntry 10 }

okay so the THD readings are up next, and they're giving main character energy ๐Ÿ’… the wyephase and delphase tables are sparse extensions hanging off the main table, so they're kinda like side quests ๐Ÿฆ‹ and then the compliance statement lays out the rules for who gets the gold star ๐ŸŒˆ let's go bestie โœจ

   eoACPwrAttributesThdCurrent OBJECT-TYPE
       SYNTAX          Integer32 (0..10000)
       UNITS           "hundredths of percent"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A calculated value for the current total harmonic
          distortion (THD).  Method of calculation is not
          specified.  IEC 61850-7-4 attribute 'ThdAmp'."
       ::= { eoACPwrAttributesEntry 11 }

   eoACPwrAttributesThdVoltage OBJECT-TYPE
       SYNTAX          Integer32 (0..10000)
       UNITS           "hundredths of percent"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A calculated value for the voltage total harmonic
          distortion (THD).  The method of calculation is not
          specified.  IEC 61850-7-4 attribute 'ThdVol'."
       ::= { eoACPwrAttributesEntry 12 }

   eoACPwrAttributesDelPhaseTable OBJECT-TYPE
       SYNTAX          SEQUENCE OF EoACPwrAttributesDelPhaseEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This optional table describes three-phase power attributes
          measurements in a DEL configuration with phase-to-phase
          power attributes measurements.  Entities having single
          phase power shall not have any entities.  This is a
          sparse extension of the eoACPwrAttributesTable.

          These attributes correspond to measurements related to
          the IEC 61850-7.4 MMXU phase and measured harmonic or
          interharmonics related to the MHAI phase."
       ::= { powerAttributesMIBObjects 2 }

   eoACPwrAttributesDelPhaseEntry OBJECT-TYPE
       SYNTAX          EoACPwrAttributesDelPhaseEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "An entry describes power measurements of a phase in a
          DEL three-phase power.  Three entries are required for each
          supported entPhysicalIndex entry.  Voltage measurements
          are provided relative to each other.

          For phase-to-phase measurements, the
          eoACPwrAttributesDelPhaseIndex is compared against the
          following phase at +120 degrees.  Thus, the possible
          values are:

          eoACPwrAttributesDelPhaseIndex    Next Phase Angle
                                0                 120
                               120                240
                               240                  0
          "
       INDEX { entPhysicalIndex, eoACPwrAttributesDelPhaseIndex }
       ::= { eoACPwrAttributesDelPhaseTable 1}

   EoACPwrAttributesDelPhaseEntry ::= SEQUENCE {
       eoACPwrAttributesDelPhaseIndex                   Integer32,
       eoACPwrAttributesDelPhaseToNextPhaseVoltage      Integer32,
       eoACPwrAttributesDelThdPhaseToNextPhaseVoltage   Integer32
                                      }

   eoACPwrAttributesDelPhaseIndex OBJECT-TYPE
       SYNTAX          Integer32 (0..359)
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "A phase angle typically corresponding to 0, 120, 240."
        ::= { eoACPwrAttributesDelPhaseEntry 1 }

   eoACPwrAttributesDelPhaseToNextPhaseVoltage OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "0.1 Volt AC"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value of phase to next phase voltages, where
          the next phase is IEC 61850-7-4 attribute 'PPV'."
       ::= { eoACPwrAttributesDelPhaseEntry 2 }

   eoACPwrAttributesDelThdPhaseToNextPhaseVoltage OBJECT-TYPE
       SYNTAX          Integer32 (0..10000)
       UNITS           "hundredths of percent"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A calculated value for the voltage total harmonic
          distortion for phase to next phase.  Method of calculation
          is not specified.  IEC 61850-7-4 attribute 'ThdPPV'."
       ::= { eoACPwrAttributesDelPhaseEntry 3 }

   eoACPwrAttributesWyePhaseTable OBJECT-TYPE
       SYNTAX          SEQUENCE OF EoACPwrAttributesWyePhaseEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This optional table describes three-phase power attributes
          measurements in a WYE configuration with phase-to-neutral
          power attributes measurements.  Entities having single
          phase power shall not have any entities.  This is a sparse
          extension of the eoACPwrAttributesTable.

          These attributes correspond to measurements related to
          the IEC 61850-7.4 MMXU phase and measured harmonic or
          interharmonics related to the MHAI phase."
       ::= { powerAttributesMIBObjects 3 }

   eoACPwrAttributesWyePhaseEntry OBJECT-TYPE
       SYNTAX          EoACPwrAttributesWyePhaseEntry
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "This table describes measurements of a phase in a WYE
          three-phase power system.  Three entries are required for
          each supported entPhysicalIndex entry.  Voltage
          measurements are relative to neutral.

          Each entry describes power attributes of one phase of a
          WYE three-phase power system."
       INDEX { entPhysicalIndex, eoACPwrAttributesWyePhaseIndex }
       ::= { eoACPwrAttributesWyePhaseTable 1}

   EoACPwrAttributesWyePhaseEntry ::= SEQUENCE {
        eoACPwrAttributesWyePhaseIndex            Integer32,
        eoACPwrAttributesWyePhaseToNeutralVoltage  Integer32,
        eoACPwrAttributesWyeCurrent              Integer32,
        eoACPwrAttributesWyeActivePower            Integer32,
        eoACPwrAttributesWyeReactivePower          Integer32,
        eoACPwrAttributesWyeApparentPower          Integer32,
        eoACPwrAttributesWyePowerFactor            Integer32,
        eoACPwrAttributesWyeThdCurrent            Integer32,
        eoACPwrAttributesWyeThdPhaseToNeutralVoltage Integer32
                                      }

   eoACPwrAttributesWyePhaseIndex OBJECT-TYPE
       SYNTAX          Integer32 (0..359)
       MAX-ACCESS      not-accessible
       STATUS          current
       DESCRIPTION
          "A phase angle typically corresponding to 0, 120, 240."
        ::= { eoACPwrAttributesWyePhaseEntry 1 }

   eoACPwrAttributesWyePhaseToNeutralVoltage OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "0.1 Volt AC"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value of phase to neutral voltage.  IEC
          61850-7-4 attribute 'PNV'."
       ::= { eoACPwrAttributesWyePhaseEntry 2 }

   eoACPwrAttributesWyeCurrent OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "0.1 amperes AC"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value of phase currents.  IEC 61850-7-4
          attribute 'A'."
       ::= { eoACPwrAttributesWyePhaseEntry 3 }

   eoACPwrAttributesWyeActivePower OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "watts"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION

          "A measured value of the actual power delivered to or
          consumed by the load with the magnitude indicated
          separately in eoPowerUnitMultiplier.  IEC 61850-7-4
          attribute 'W'."
       ::= { eoACPwrAttributesWyePhaseEntry 4 }

   eoACPwrAttributesWyeReactivePower OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "volt-amperes reactive"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value of the reactive portion of the apparent
          power with the magnitude of indicated separately in
          eoPowerUnitMultiplier.  IEC 61850-7-4 attribute 'VAr'."
       ::= { eoACPwrAttributesWyePhaseEntry 5 }

   eoACPwrAttributesWyeApparentPower OBJECT-TYPE
       SYNTAX          Integer32
       UNITS           "volt-amperes"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value of the voltage and current determines
          the apparent power with the indicated separately in
          eoPowerUnitMultiplier.  Active plus reactive power equals
          the total apparent power.

          Note: Watts and volt-amperes are equivalent units and may
          be combined.  IEC 61850-7-4 attribute 'VA'."
       ::= { eoACPwrAttributesWyePhaseEntry 6 }

   eoACPwrAttributesWyePowerFactor OBJECT-TYPE
       SYNTAX          Integer32 (-10000..10000)
       UNITS           "hundredths"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A measured value ratio of the real power flowing to the
          load versus the apparent power for this phase.  IEC
          61850-7-4 attribute 'PF'.  Power Factor can be positive or
          negative where the sign should be in lead/lag (IEEE)
          form."
       ::= { eoACPwrAttributesWyePhaseEntry 7 }

   eoACPwrAttributesWyeThdCurrent OBJECT-TYPE
       SYNTAX          Integer32 (0..10000)
       UNITS           "hundredths of percent"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A calculated value for the voltage total harmonic
          distortion (THD) for phase to phase.  Method of
          calculation is not specified.
          IEC 61850-7-4 attribute 'ThdA'."
       ::= { eoACPwrAttributesWyePhaseEntry 8 }

   eoACPwrAttributesWyeThdPhaseToNeutralVoltage OBJECT-TYPE
       SYNTAX          Integer32 (0..10000)
       UNITS           "hundredths of percent"
       MAX-ACCESS      read-only
       STATUS          current
       DESCRIPTION
          "A calculated value of the voltage total harmonic
          distortion (THD) for phase to neutral.  IEC 61850-7-4
          attribute 'ThdPhV'."
       ::= { eoACPwrAttributesWyePhaseEntry 9 }

   -- Conformance
   powerAttributesMIBCompliances  OBJECT IDENTIFIER
       ::= { powerAttributesMIB 2 }

   powerAttributesMIBGroups  OBJECT IDENTIFIER
       ::= { powerAttributesMIB 3 }

   powerAttributesMIBFullCompliance MODULE-COMPLIANCE
       STATUS          current
       DESCRIPTION
          "When this MIB is implemented with support for read-
          create, then such an implementation can claim full
          compliance.  Such devices can then be both monitored and
          configured with this MIB.

          Module Compliance of RFC 6933 with respect to
          entity4CRCompliance MUST be supported which requires
          implementation of four MIB objects: entPhysicalIndex,
          entPhysicalClass, entPhysicalName, and entPhysicalUUID."
       REFERENCE
          "RFC 6933: Entity MIB (Version 4)"

       MODULE          -- this module
       MANDATORY-GROUPS {
                        powerACPwrAttributesMIBTableGroup
                                 }

       GROUP        powerACPwrAttributesOptionalMIBTableGroup
       DESCRIPTION
          "A compliant implementation does not have
          to implement."

       GROUP       powerACPwrAttributesDelPhaseMIBTableGroup
       DESCRIPTION
           "A compliant implementation does not have to implement."

       GROUP       powerACPwrAttributesWyePhaseMIBTableGroup
       DESCRIPTION
           "A compliant implementation does not have to implement."
       ::= { powerAttributesMIBCompliances 1 }

   -- Units of Conformance
   powerACPwrAttributesMIBTableGroup OBJECT-GROUP
       OBJECTS         {
                  -- Note that object entPhysicalIndex is NOT
                    -- included since it is not-accessible
                           eoACPwrAttributesAvgVoltage,
                           eoACPwrAttributesAvgCurrent,
                           eoACPwrAttributesFrequency,
                           eoACPwrAttributesPowerUnitMultiplier,
                           eoACPwrAttributesPowerAccuracy,
                           eoACPwrAttributesTotalActivePower,
                           eoACPwrAttributesTotalReactivePower,
                           eoACPwrAttributesTotalApparentPower,
                           eoACPwrAttributesTotalPowerFactor
                                               }
       STATUS          current
       DESCRIPTION
          "This group contains the collection of all the power
          attributes objects related to the Energy Object."
       ::= { powerAttributesMIBGroups  1 }

    powerACPwrAttributesOptionalMIBTableGroup OBJECT-GROUP
       OBJECTS         {
                           eoACPwrAttributesConfiguration,
                           eoACPwrAttributesThdCurrent,
                           eoACPwrAttributesThdVoltage
                       }
       STATUS          current
       DESCRIPTION
          "This group contains the collection of all the power
          attributes objects related to the Energy Object."
       ::= { powerAttributesMIBGroups  2 }

   powerACPwrAttributesDelPhaseMIBTableGroup OBJECT-GROUP

       OBJECTS         {
                       -- Note that object entPhysicalIndex and
                       -- eoACPwrAttributesDelPhaseIndex are NOT
                       -- included since they are not-accessible
                 eoACPwrAttributesDelPhaseToNextPhaseVoltage,
                 eoACPwrAttributesDelThdPhaseToNextPhaseVoltage
                       }
       STATUS          current
       DESCRIPTION
          "This group contains the collection of all power
          attributes of a phase in a DEL three-phase power system."
       ::= { powerAttributesMIBGroups 3 }

   powerACPwrAttributesWyePhaseMIBTableGroup OBJECT-GROUP
       OBJECTS         {
                          -- Note that object entPhysicalIndex and
                          -- eoACPwrAttributesWyePhaseIndex are NOT
                          -- included since they are not-accessible
                  eoACPwrAttributesWyePhaseToNeutralVoltage,
                  eoACPwrAttributesWyeCurrent,
                  eoACPwrAttributesWyeActivePower,
                  eoACPwrAttributesWyeReactivePower,
                  eoACPwrAttributesWyeApparentPower,
                  eoACPwrAttributesWyePowerFactor,
                  eoACPwrAttributesWyeThdPhaseToNeutralVoltage,
                  eoACPwrAttributesWyeThdCurrent
                       }
       STATUS          current
       DESCRIPTION
          "This group contains the collection of all power
          attributes of a phase in a WYE three-phase power system."
       ::= { powerAttributesMIBGroups 4 }

   END

10. Security Considerations ๐Ÿ”

Okay bestie, this part is serious, so let's get into it ๐Ÿซถ. There are a bunch of management objects in this MIB module that have a MAX-ACCESS clause of read-write and/or read-create. These objects can be sensitive or vulnerable in some network environments ๐Ÿ™ˆ. Supporting SET operations in a non-secure environment, without proper protection, opens devices up to attack ๐Ÿ’€. Here are the tables and objects, plus how sensitive or vulnerable they are:

  • Unauthorized changes to the eoPowerOperState (via the eoPowerAdminState ) MAY disrupt the power settings of the differentEnergy Objects and, therefore, the state of functionality of the respective Energy Objects.
  • Unauthorized changes to the eoEnergyParametersTable MAY disrupt energy measurement in the eoEnergyTable table.

Real talk, SNMP versions before SNMPv3 did not have adequate security ๐Ÿ˜ญ. Even if the network itself is secure (for example, by using IPsec), there is no control over who on that secure network is allowed to access and GET/SET (read/change/create/delete) the objects in this MIB module. Not me being like "wait, anyone can just change it?" ๐Ÿ’…

Implementations SHOULD provide the security features described by the SNMPv3 framework (see [RFC3410]). Implementations that claim compliance with the SNMPv3 standard MUST include full support for authentication and privacy via the User-based Security Model (USM) [RFC3414] with the AES cipher algorithm [RFC3826]. Implementations MAY also provide support for the Transport Security Model (TSM) [RFC5591] in combination with a secure transport such as SSH [RFC5592] or TLS/DTLS [RFC6353] ๐Ÿฆ‹.

Further, deploying SNMP versions prior to SNMPv3 is NOT RECOMMENDED ๐Ÿ™…โ€โ™€๏ธ. Instead, it is RECOMMENDED to deploy SNMPv3 and to enable cryptographic security ๐Ÿ”ฅ. It is then a customer/operator responsibility to make sure that the SNMP entity giving access to an instance of this MIB module is properly configured, so access to the objects is only given to those principals (users) who have legitimate rights to actually GET or SET (change/create/delete) them ๐Ÿ‘‘.

Energy and power monitoring can reveal sensitive information about individuals' activities and habits. That's giving privacy alarm ๐Ÿšจ. Implementors of this specification should use appropriate privacy protections as discussed in Section 9 of RFC 6988, and monitoring of individuals and homes should only occur with proper authorization ๐ŸŒธ.

11. IANA Considerations ๐ŸŒˆ

The MIB modules in this document use the following IANA-assigned OBJECT IDENTIFIER values, which are recorded in the SMI Numbers registry ๐Ÿงš:

   Descriptor                   OBJECT IDENTIFIER value
   ----------                   -----------------------

   IANAPowerStateSet-MIB           { mib-2 228 }

   energyObjectMIB                 { mib-2 229 }

   powerAttributesMIB              { mib-2 230 }

11.1. IANAPowerStateSet-MIB Module ๐Ÿ“

The initial set of Power State Sets is specified in [RFC7326]. IANA maintains a Textual Convention PowerStateSet in the IANAPowerStateSet-MIB module (see Section 9.1), with the initial set of Power State Sets and the Power States within those Power State Sets as proposed in [RFC7326]. The current version of the PowerStateSet Textual Convention can be accessed at <http://www.iana.org/assignments/power-state-sets>.

New assignments (and potential deprecation) to Power State Sets shall be administered by IANA. The guidelines and procedures are specified in [RFC7326], and they will, as a consequence, update the PowerStateSet Textual Convention โœจ.

12. References ๐Ÿ“š

12.1. Normative References ๐Ÿ’œ

12.2. Informative References โœจ

okay bestie, these are the "extra reading" refs ๐Ÿ“š they're not required to implement the thing, but they're the background the whole spec is built on. they're all in the code block below, copied exactly as written so nothing gets lost ๐Ÿ’…

[RFC1628]       Case, J., Ed., "UPS Management Information Base", RFC
                1628, May 1994,
                <http://www.rfc-editor.org/info/rfc1628>.

[RFC3410]       Case, J., Mundy, R., Partain, D., and B. Stewart,
                "Introduction and Applicability Statements for
                Internet-Standard Management Framework", RFC 3410,
                December 2002,
                <http://www.rfc-editor.org/info/rfc3410>.

[RFC3418]       Presuhn, R., Ed., "Management Information Base (MIB)
                for the Simple Network Management Protocol (SNMP)",
                STD 62, RFC 3418, December 2002,
                <http://www.rfc-editor.org/info/rfc3418>.

[RFC3433]       Bierman, A., Romascanu, D., and K. Norseth, "Entity
                Sensor Management Information Base", RFC 3433,
                December 2002,
                <http://www.rfc-editor.org/info/rfc3433>.

[RFC4268]       Chisholm, S. and D. Perkins, "Entity State MIB", RFC
                4268, November 2005,
                <http://www.rfc-editor.org/info/rfc4268>.

[RFC6988]       Quittek, J., Ed., Chandramouli, M., Winter, R.,
                Dietz, T., and B. Claise, "Requirements for Energy
                Management", RFC 6988, September 2013,
                <http://www.rfc-editor.org/info/rfc6988>.

[RFC7326]       Parello, J., Claise, B., Schoening, B., and J.
                Quittek, "Energy Management Framework", RFC 7326,
                September 2014,
                <http://www.rfc-editor.org/info/rfc7326>.

[DMTF]          DMTF, "Power State Management Profile", DSP1027,
                Version 2.0, December 2009,
                http://www.dmtf.org/sites/default/files/standards
                /documents/DSP1027_2.0.0.pdf

[EMAN-AS]       Schoening, B., Chandramouli, M., and B. Nordman,
                "Energy Management (EMAN) Applicability Statement",
                Work in Progress, draft-ietf-eman-applicability-
                statement-08, December 2014.

[IEC.61850-7-4] International Electrotechnical Commission,
                "Communication networks and systems for power utility
                automation  -- Part 7-4: Basic communication
                structure  -- Compatible logical node classes and
                data object classes", March 2010.

[IEC.62053-21]  International Electrotechnical Commission,
                "Electricity metering equipment (a.c.) -- Particular
                requirements -- Part 21: Static meters for active
                energy (classes 1 and 2)", January 2003.

[IEC.62053-22]  International Electrotechnical Commission,
                "Electricity metering equipment (a.c.) -- Particular
                requirements -- Part 22: Static meters for active
                energy (classes 0,2 S and 0,5 S)", January 2003.

[IEEE1621]      "Standard for User Interface Elements in Power
                Control of Electronic Devices Employed in
                Office/Consumer Environments", IEEE 1621, December
                2004.

Acknowledgments ๐Ÿซถ

okay the shoutouts ๐Ÿฅน the authors want to thank Shamita Pisal for her prototype of this MIB module and her super valuable feedback ๐Ÿ’– they also want to thank Michael Brown for making the text so much better, like dramatically better โœจ

Juergen Schoenwalder gets a big thank you for proposing the design of the Textual Convention for PowerStateSet, and Ira McDonald gets one for his feedback ๐ŸŒธ Laurent Guise deserves special appreciation for reviewing and weighing in on power quality measurements โšก and Minoru Teraoka and Hiroto Ogaki get thanks for all the comments on the design of the EnergyTable ๐ŸŽ€

Alan Luchuk gets a huge thank you for the detailed review of the MIB and his comments ๐Ÿ”ฅ

And finally, thanks to the EMAN chairs, Nevil Brownlee and Tom Nadeau ๐Ÿ‘‘ the real MVPs ๐Ÿงš


Contributors ๐ŸŒˆ

this document is literally the result of two separate starter proposals getting merged together ๐Ÿฆ‹ the people below made big contributions, either to one of the original proposals or to this document itself:

John Parello

Rolf Winter

Dominique Dudkowski

Authors' Addresses ๐Ÿ’…

and here are the people who actually wrote it, with their addresses and contact info, copied exactly so you can reach them ๐Ÿ“ฌ

Mouli Chandramouli
Cisco Systems, Inc.
Sarjapur Outer Ring Road
Bangalore 560103
India
Phone: +91 80 4429 2409
EMail: moulchan@cisco.com


Benoit Claise
Cisco Systems, Inc.
De Kleetlaan 6a b1
Diegem 1813
Belgium
Phone: +32 2 704 5622
EMail: bclaise@cisco.com


Brad Schoening
44 Rivers Edge Drive
Little Silver, NJ 07739
United States
EMail: brad.schoening@verizon.net


Juergen Quittek
NEC Europe, Ltd.
NEC Laboratories Europe
Network Research Division
Kurfuersten-Anlage 36
Heidelberg  69115
Germany
Phone: +49 6221 4342-115
EMail: quittek@neclab.eu


Thomas Dietz
NEC Europe, Ltd.
NEC Laboratories Europe
Network Research Division
Kurfuersten-Anlage 36
Heidelberg  69115
Germany
Phone: +49 6221 4342-128
EMail: Thomas.Dietz@neclab.eu

and that's the whole spec, bestie ๐ŸŒˆโœจ you made it through all 13 parts ๐Ÿ˜ญ๐Ÿซถ