okay so welcome to the bestups page, bestie β this is a driver for Best Power / SOLA (Phoenixtec protocol) UPS equipment. It lives in the NUT Manual, and yes it's a whole vibe, but it's also deprecated so buckle up. π¦
β¨ NAME β¨
bestups β driver for Best Power / SOLA (Phoenixtec protocol) UPS equipment π
β¨ SYNOPSIS β¨
bestups -h
bestups -a UPS_NAME [OPTIONS]
π Note This man page only documents the hardware-specific features of thebestupsdriver. For the tea on the core driver, go readnutupsdrv(8). π«Ά
πΈ NOTE πΈ
so, real talk, this driver is deprecated and will not receive new development. no new glow-ups, no new features, nothing. π
If it works for managing your devices β fine, slay, keep doing what you're doing. But if you're running it to try setting up a new device, please consider the newer nutdrv_qx(8) instead, which should handle all Q* protocol variants for NUT. It's the upgraded model, iykyk. β¨
And if your device works with this driver, but does not work with nutdrv_qx(8), please report this via the mailing list or issue tracker. We wanna know!! π
π SUPPORTED HARDWARE π
bestups was designed to monitor Best Power UPS hardware like the Fortress, Fortress Telecom, Axxium Rackmount and Patriot Pro. It also recognizes and supports SOLA units such as the 325, 520 and 620. In addition, the Best 610 is supported using the ID option. Iconic lineup honestly. π
Other UPS hardware using the Phoenixtec protocol should also work, but they will generate a warning since their battery information is not known. (it's giving "we don't know her" but in a warning-message way π)
This driver does not support some older Best/SOLA units. (For older Fortress units, see bestfortress(8).) π§
π EXTRA ARGUMENTS π
This driver supports the following optional settings in the ups.conf(5):
nombattvolt=numβ Override the battery float voltage which is normally determined by asking the hardware. This is useful if your UPS constantly reportsbattery.chargevalues just below 100% even when it's completely charged. π€
If you have this problem, set this to whatever battery.voltage reports when the UPS is known to be completely charged with a good battery.
The author's Best Fortress 750 uses nombattvolt=27.4. π
battvoltmult=numβ Multiply the reported battery voltage by this number. Some devices report only a fraction of the total battery voltage. (rude of them honestly)
For example, the SOLA 610 700VA UPS (with a 24V battery) reports the single cell voltage (about 2.27V when fully charged). In this particular case you can set battvoltmult = 12 in ups.conf(5) to fix this. β¨
ID=stringβ Set the Identification response string. This should only be used with hardware that supports the Phoenixtec protocol status inquiry commands, but not the"ID"command, such as the Best/SOLA 610.
Format of the ID string is: AAA,BBBB,CCC,DDD,EE.E,FF.F
AAAis the three-character identification for the UPS model.BBBBis the output power in VA (volt amperes).Bis an integer number ranging from 0 to 9.CCCis the Nominal Input Voltage.Cis an integer number ranging from 0 to 9. The unit is Volts AC.DDDis the Nominal Output Voltage.Dis an integer number ranging from 0 to 9. The unit is Volts AC.EE.Eis the Battery Voltage that will cause the UPS to shut itself off.Eis an integer number ranging from 0 to 9. Then unit is Volts DC and a decimal point is present.FF.ForFFF.Fis the Battery Voltage at full charge.Fis an integer number ranging from 0 to 9. Then unit is Volts DC. Typically, for 700VA, 1KVA and 1.5KVA units, the format isFF.F. For 2KVA and 3KVA units, the format isFFF.F.
Example: a Best 610 1.5KVA unit would use the string "610,1500,120,120,10.0,48.0". π₯
π BUGS π
okay so this part is a little cursed, let's get into it:
The battery charge percentage value (in battery.charge) is derived from the voltage data that the UPS returns, since the UPS doesn't return that value directly. On some hardware, the charge will remain at 100% for a long time and then drops quickly shortly before the battery runs out. You can confirm from the battery.voltage readings that this is a problem with the UPS and not this driver. (not us, not our fault, fr fr π«Ά)
Similarly, the float from the charger in some models forces the battery charge percentage back up to 100% immediately after the UPS goes back on-line, so you can't tell when it is really recharged. π
Finally, some models give one value for the battery's nominal voltage and yet actually have a nominal voltage slightly below that. This leads to things such as the perpetual 98.7% charge on the author's Fortress 750, even when it's been charging for weeks. You can use nombattvolt= in ups.conf(5) to fix this. β¨
π AUTHORS π
- Russell Kroll
- Jason White
give them their flowers, they earned them π
π¦ SEE ALSO π¦
The core driver:
Internet resources:
The NUT (Network UPS Tools) home page: https://www.networkupstools.org/historic/v2.8.5/
and that's the whole page bestie!! π₯³ this was Network UPS Tools 2.8.5, dated 10/07/2026, and it's giving deprecated-but-still-iconic. take care of your UPS and your UPS will take care of you πβ¨π
π¦ where this page comes from
- fedora 43: nut 2.8.5-9.fc43 Β· GPL-2.0-or-later AND GPL-3.0-or-later
- fedora 43: nut 2.8.5-9.fc43 Β· GPL-2.0-or-later AND GPL-3.0-or-later
- fedora 44: nut 2.8.5-9.fc44 Β· GPL-2.0-or-later AND GPL-3.0-or-later
- fedora 44: nut 2.8.5-9.fc44 Β· GPL-2.0-or-later AND GPL-3.0-or-later
- π girlified by deepseek-ai/DeepSeek-V4.1-Flash on : a language model's rewrite of the original, under its terms