โœจ SYNOPSIS โœจ

nutdrv_qx -h

nutdrv_qx -a UPS_NAME [OPTIONS]
Note ๐Ÿ“Œ This man page only documents the hardware-specific features of the nutdrv_qx driver. For information about the core driver, see nutupsdrv(8).

๐Ÿ”Œ SUPPORTED HARDWARE ๐Ÿ”Œ

so the lore is: this protocol originates from Mega System Technologies, Inc. in Taiwan ๐Ÿ‡น๐Ÿ‡ผ, and it got used by sooo many vendors, and it evolved over time, growing both in features and in nuanced incompatibilities. (character development, but make it firmware ๐Ÿ’€). NUT documentation usually refers to this large family of similar dialects as the Megatec Q* or Megatec Qx protocol family.

The nutdrv_qx driver is known to work with various UPSes from Armac, Blazer, Energy Sistem, Fenton Technologies, General Electric, Gtec, Hunnox, Masterguard, Mustek, Powercool, Voltronic Power, SKE (rebranded by many, many โ€” have I said many? โ€” others...

Long story short: if your UPS came with a software called Viewpower, chances are high that it works with this driver with one of the voltronic* protocols or with the mecer one), and many others.

Note ๐Ÿ‘€ Due to historical reasons, two important tunables of this driver are somewhat inconveniently named protocol (for the Qx dialect) and subdriver (for USB to serial link conversion). Other multi-dialect drivers refer to their dialect modules as subdrivers, and actually the modular source code of nutdrv_qx also does.
Note โณ Due to the amount of supported Qx dialects, and the time it takes to query for relevant combinations of commands and wait for a reply or absence thereof, in order to detect hardware/firmware support of some particular way for the driver to communicate with the device, automatic nutdrv_qx driver initialization may take about a minute. It is recommended to store the detected and reported protocol and/or subdriver values into your ups.conf(5) file to speed up later driver start-ups and avoid possible service timeouts.

The NUT compatibility table lists all the known supported models. Keep in mind, however, that other models not listed there may also be supported, but haven't been tested or reported back.

All devices with a serial interface and many with a USB interface are supported. ๐Ÿ’…


๐ŸŽ€ EXTRA ARGUMENTS ๐ŸŽ€

You may need to override or provide defaults for some values, depending on the make and model of your UPS.

The following are the ones that most likely will need changing (see ups.conf(5)):

  • ondelay = value โ€” Time to wait before switching on the UPS (seconds). This value is truncated to units of 60 seconds.

Note that a value below 3 minutes, may cause earlier firmware versions to not switch on automatically, so it defaults to 3 minutes (i.e. 180 seconds).

This option provides a default value for ups.delay.start that will then be used by the driver in the automatic shutdown sequence (i.e. calling the driver with the -k option, calling upsdrvctl(8) with the shutdown option or when the FSD flag is set and upsmon(8) enters its shutdown sequence): however you can change this value 'on the fly' for the actual session, only for the use with instant commands, setting ups.delay.start with upsrw(8).

  • offdelay = value โ€” Time to wait before shutting down the UPS (seconds). This value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds (more than 60 seconds). Defaults to 30 seconds.

This option provides a default value for ups.delay.shutdown that will then be used by the driver in the automatic shutdown sequence (i.e. calling the driver with the -k option, calling upsdrvctl(8) with the shutdown option or when the FSD flag is set and upsmon(8) enters its shutdown sequence): however you can change this value "on the fly" for the actual session, only for the use with instant commands, setting ups.delay.shutdown with upsrw(8).

  • stayoff โ€” If you set stayoff in ups.conf(5) when FSD arises the UPS will call a shutdown.stayoff shutting down after ups.delay.shutdown seconds and won't return (see KNOWN PROBLEMS), otherwise (standard behaviour) the UPS will call shutdown.return shutting down after ups.delay.shutdown seconds and then turn on after ups.delay.start seconds (if mains meanwhile returned).
  • protocol = string โ€” Skip autodetection of the protocol to use and only use the one specified. Supported values: bestups, gtec, hunnox, innovart31, innovart33, innovatae, masterguard, mecer, megatec, megatec/old, mustek, q1, q2, q6, voltronic, voltronic-axpert, voltronic-qs, voltronic-qs-hex and zinto.

Run the driver program with the --help option to see the exact list of protocol values it would currently recognize.

Note that if you end up using the q1 protocol, you may want to give a try to the mecer, megatec and zinto ones setting the novendor/norating flags (only one, or both).

  • pollfreq = num โ€” Set polling interval for full updates, in seconds, to reduce the message traffic. Between two polling requests, the driver will do quick polls dealing just with ups.status at an interval specified by the pollinterval driver option (details in ups.conf(5)). The default value is 30 (in seconds).

If your UPS doesn't report either battery.charge or battery.runtime you may want to add the following ones in order to have guesstimated values:

  • default.battery.voltage.high = value โ€” Maximum battery voltage that is reached after about 12 to 24 hours charging. If you want the driver to report a guesstimated battery.charge, you need to specify this (see BATTERY CHARGE GUESSTIMATION).
  • default.battery.voltage.low = value โ€” Minimum battery voltage just before the UPS automatically shuts down. If you want the driver to report a guesstimated battery.charge, you need to specify this (see BATTERY CHARGE GUESSTIMATION).
  • default.battery.voltage.nominal = value, override.battery.voltage.nominal = value โ€” Some devices show a wrong nominal battery voltage (or none at all), so you may need to override or set a default value.
  • override.battery.packs = value โ€” Some devices "natively" report just a part of the total battery voltage (see also battery_voltage_reports_one_pack below).

For instance, if battery.voltage.nominal is 24 V, but it reports a battery.voltage of around 2 V, the number of battery.packs to correct this reading would be 12.

The driver will attempt to detect this number automatically, but if this fails somehow, you may want to override this value.

Note that this is primarily useful for "guesstimation" of battery.charge and/or battery.runtime (with runtimecal setting), if those readings are not provided by the device directly.

  • battery_voltage_reports_one_pack โ€” Some devices "natively" report just report a part of the total battery voltage (see also override.battery.packs above, if that value is not reported by the device or properly guessed by the driver otherwise).

If this flag is set, most of the subdrivers (except those which know about more complicated device-specific nuances, currently: ablerex, masterguard and voltronic-qs-hex) adjust their ultimately reported battery.voltage value as a multiple of battery.packs and "native" battery.voltage).

Note this is primarily useful for consistent diagnostics and graphing of the numbers, and should not impact the "guesstimation" of battery.charge and/or battery.runtime โ€” so rather a cosmetic adjustment, than critical.

  • runtimecal = value,value,value,value โ€” Parameter used in the (optional) runtime estimation. This takes two runtimes at different loads. Typically, this uses the runtime at full load and the runtime at half load. For instance, if your UPS has a rated runtime of 240 seconds at full load and 720 seconds at half load, you would enter
runtimecal = 240,100,720,50

The first load should always be higher than the second. If you have values available for loads other than 100 and 50 % respectively, you can use those too, but keep them spaced apart as far as reasonably possible. Just don't get too close to no load (prediction of runtime depends more on idle load for the battery then).

  • chargetime = value โ€” The time needed to fully recharge the battery after being fully discharged. If not specified, the driver defaults to 43200 seconds (12 hours). Only used if runtimecal is also specified.
  • idleload = value โ€” Minimum battery load used by the driver to estimate the runtime. If not specified, the driver defaults to 10%. Only used if runtimecal is also specified.

๐Ÿ’ซ BESTUPS, INNOVART31, INNOVART33, INNOVATAE, MECER, MEGATEC, MEGATEC/OLD, MUSTEK, Q1, Q2, Q6, VOLTRONIC-QS, VOLTRONIC-QS-HEX, ZINTO PROTOCOLS ๐Ÿ’ซ

  • ignoresab โ€” Some UPSes incorrectly report the 'Shutdown Active' bit as always on, consequently making the driver believe the UPS is nearing a shutdown (and, as a result, ups.status always contains FSD... and you know what this means). Setting this flag will make the driver ignore the 'Shutdown Active' bit.

๐ŸŒธ MECER, MEGATEC, MEGATEC/OLD, MUSTEK, ZINTO PROTOCOLS ๐ŸŒธ

  • ondelay โ€” The acceptable range is 0..599940 seconds.
  • offdelay โ€” The acceptable range is 12..600 seconds.
  • norating โ€” Some UPSes will lock up if you attempt to read rating information from them. Setting this flag will make the driver skip this step.
  • novendor โ€” Some UPSes will lock up if you attempt to read vendor information from them. Setting this flag will make the driver skip this step.

๐Ÿงš BESTUPS PROTOCOL ๐Ÿงš

  • ondelay โ€” The acceptable range is 60..599940 seconds.
  • offdelay โ€” The acceptable range is 12..5940 seconds.
  • pins_shutdown_mode = value โ€” Set shutdown mode functionality of Pin 1 and Pin 7 on the UPS DB9 communication port (Per Best Power's EPS-0059) to value [0..6].

๐Ÿ‘‘ MASTERGUARD PROTOCOL ๐Ÿ‘‘

  • slave_addr = value โ€” Make the claim function verify it's talking to the specified slave address (ups.id). Safeguard against talking to the wrong one of several identical UPSes on the same USB bus. Note that when changing ups.id (through upsrw(8)) the driver will continue to talk to the UPS with the new slave address, but won't claim it again on restart until the slave_addr parameter is adjusted.

๐Ÿ“ INNOVART31, INNOVART33, INNOVATAE, Q1, Q2, Q6 PROTOCOLS ๐Ÿ“

  • ondelay โ€” The acceptable range is 0..599940 seconds.
  • offdelay โ€” the acceptable range is 12..600 seconds. that's the whole vibe, bestie โœจ

Q2, Q6 PROTOCOLS ๐ŸŽ€

  • nooutstats โ€” okay so some UPSes just don't support the WA command, which is the one that returns output load stats. flip this flag on and the driver will straight up ignore those requests. no drama, no error spam. ๐Ÿ’…

VOLTRONIC-QS, VOLTRONIC-QS-HEX PROTOCOLS ๐Ÿฆ‹

  • ondelay โ€” acceptable range is 60..599940 seconds. yes, that's a lot of seconds, she's got range ๐ŸŒธ
  • offdelay โ€” acceptable range is 12..540 seconds.

VOLTRONIC-AXPERT PROTOCOL ๐Ÿ‘‘

Note โ€” this protocol is currently largely experimental, and many features may be only exposed in specially configured builds of the NUT driver program. iykyk, don't come for me if it's weird ๐Ÿ™ˆ
  • reset_to_default โ€” resets capability options and their limits to safe default values.
  • bypass_alarm โ€” alarm (BEEP! ๐Ÿ””) at Bypass Mode [enabled/disabled].
  • battery_alarm โ€” alarm (BEEP! ๐Ÿ””) at Battery Mode [enabled/disabled].

VOLTRONIC PROTOCOL ๐Ÿ’–

the following options are supported only by the voltronic protocol. and ngl? not all of them are available on all the UPSes supported by this protocol. it's giving "check your device first" ๐Ÿซถ

  • ondelay โ€” acceptable range is 0..599940 seconds.
  • offdelay โ€” acceptable range is 12..5940 seconds.
  • battery_number = value โ€” sets the number of batteries that make a pack to value [1..9]. heads up bestie, this setting will change the charge and runtime estimation reported by the UPS. so like, she's not lying to you, she's just recalibrating ๐Ÿ’…
  • output_phase_angle = value โ€” changes the output phase angle to the provided value [000, 120, 180, 240]ยฐ. iconic little degree symbol, keeping it exactly as it is โœจ

UPS CAPABILITY SETTINGS ๐ŸŽ€

  • reset_to_default โ€” resets capability options and their voltage and frequency limits to safe default values. (doable only when the UPS is in Standby Mode โญ)
note that setting this option will also reset ups.start.auto, battery.protection, battery.energysave, ups.start.battery, outlet.0.switchable, input.transfer.high, input.transfer.low, input.frequency.high and input.frequency.low. like, all of them. every single one. ๐Ÿ’€

these UPSes can be fine-tuned to suit your needs by enabling or disabling the following options โ€” and the driver should tell you which one the UPS is capable of on startup: the settable ones will be reported either as enabled or disabled in the logs. so check your logs, bestie, the tea is in there ๐Ÿ“

  • alarm_control = string โ€” enable or disable alarm (BEEP! ๐Ÿ””) [enabled/disabled]. settable also 'on the fly' with the beeper.enable and beeper.disable instant commands. slay โœจ
  • bypass_alarm = string โ€” enable or disable alarm (BEEP! ๐Ÿ””) at Bypass Mode [enabled/disabled].
  • battery_alarm = string โ€” enable or disable alarm (BEEP! ๐Ÿ””) at Battery Mode [enabled/disabled].
  • bypass_when_off = string โ€” enable or disable bypass when the UPS is Off [enabled/disabled]. if enabled, AC will directly provide power to connected devices when the UPS is off. main character energy fr ๐Ÿ”ฅ
  • bypass_forbidding = string โ€” enable or disable Bypass Forbidding [enabled/disabled]. if enabled, the UPS will not transfer to bypass mode under any condition. periodt, she said no ๐Ÿ’…
  • converter_mode = string โ€” enable or disable Converter Mode [enabled/disabled]. when the input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. the UPS will still charge battery under this mode. multitasking queen ๐Ÿ‘‘
  • eco_mode = string โ€” enable or disable ECO Mode [enabled/disabled]. when input voltage/frequency are within acceptable range, the UPS will bypass voltage to output for energy saving. PFC and INVERTER are still active at this mode. settable also "on the fly" with the bypass.start and bypass.stop instant commands ๐ŸŒฑ
  • advanced_eco_mode = string โ€” enable or disable Advanced ECO Mode [enabled/disabled]. when input voltage/frequency are within acceptable range, the UPS will bypass voltage to output for energy saving. PFC and INVERTER are off at this mode. that's the difference, bestie, don't mix them up ๐Ÿ’–
  • battery_open_status_check = string โ€” enable or disable Battery Open Status Check [enabled/disabled]. if enabled, when the UPS is turned on, it will check if the battery is connected or not. she's doing a vibe check on your battery ๐Ÿ”
  • site_fault_detection = string โ€” enable or disable site fault detection [enabled/disabled]. if enabled, the UPS will beep when the input neutral and hot wires are reversed. beep beep, that's your wiring being backwards ๐Ÿšจ
  • constant_phase_angle = string โ€” enable or disable Constant Phase Angle Function (output and input phase angles are not equal) [enabled/disabled].
  • limited_runtime_on_battery = string โ€” enable or disable limited runtime on battery mode [enabled/disabled].

BYPASS MODE VOLTAGE/FREQUENCY LIMITS ๐Ÿฆ‹

variables to fine-tune voltage and frequency limits for Bypass mode. these limits are reset to safe default values by reset_to_default. โญ

if AC voltage and frequency are within acceptable range, Bypass mode will be used (if the UPS is capable of and it's enabled).

since these values are device-specific, if your UPS supports them, you will get their settable limits printed in the logs on startup. logs = free lore drops ๐Ÿ“–

  • max_bypass_volt = value โ€” maximum voltage for Bypass Mode (V).
  • min_bypass_volt = value โ€” minimum voltage for Bypass Mode (V).
  • max_bypass_freq = value โ€” maximum frequency for Bypass Mode (Hz).
  • min_bypass_freq = value โ€” minimum frequency for Bypass Mode (Hz).

OPTIONS SPECIFIC FOR P31 UPSES ๐Ÿ’œ

the following options are available only on P31 UPSes.

  • work_range_type = string โ€” device grid working range for P31 UPSes [Appliance/UPS].

TESTING ๐Ÿงš

okay so this protocol comes with a couple of functions that are not enabled by default, because your friendly neighborhood developer doesn't fully know some part of the communication protocol used by these UPSes ๐Ÿ™ˆ. since these functions are supposed to be queries to the UPS for some kind of information, they should not make your UPS go boom. so if you are brave enough to risk your UPS and attached devices' life to help the developers, this will be very appreciated. do it at your own risk. ๐Ÿ‘‘

  • testing โ€” if invoked, the driver will exec also commands that still need testing.

SERIAL INTERFACE ONLY ๐ŸŒˆ

  • cablepower = string โ€” by default the driver will set DTR and clear RTS (normal). if you find that your UPS isn't detected, or the communication with the UPS is unreliable, you may try if clear DTR and set RTS (reverse), set DTR and RTS (both) or clear DTR and RTS (none) improves this situation. it's giving โœจtry all the combosโœจ ๐Ÿ’…

USB INTERFACE ONLY ๐ŸŽ€

  • port = string โ€” required option for all NUT drivers. some value must be set, typically auto for drivers that handle USB connections.
Note โ€” this could be a device filesystem path like /dev/usb/hiddev0, but current use of the libusb API precludes knowing and matching by such identifiers. they may also be inherently unreliable (dependent on re-plugging and enumeration order). at this time the actual value is ignored, but syntactically some port configuration must still be there. yes bestie, it's decorative but mandatory ๐Ÿ’€

it is possible to control multiple UPS units simultaneously by running several instances of this driver, provided they can be uniquely distinguished by setting some combination of the vendor, product, vendorid, productid, serial, bus and/or device options detailed below. for devices or operating systems that do not provide sufficient information, the allow_duplicates option can be of use (limited and risky!). ๐Ÿซถ

  • vendorid = regex, productid = regex, vendor = regex, product = regex, serial = regex โ€” select a specific UPS, in case there is more than one connected via USB. each option specifies an extended regular expression (see regex(7) for more information on regular expressions), which must match the UPS's entire respective vendor/product/serial string values (minus any surrounding whitespace), or the whole 4-digit hexadecimal code for vendorid and productid.

try lsusb(8) or running this NUT driver with the -DD command-line argument for finding out the strings to match. detective work, but make it cute ๐Ÿ”โœจ

examples:

  • -x vendor="Foo.Corporation.*"
  • -x vendorid="051d*" (APC)
  • -x product=".*(Smart|Back)-?UPS.*"
  • bus = regex โ€” OPTIONAL, NOT RECOMMENDED.

select a UPS on a specific USB bus or group of buses. the argument is a regular expression that must match the bus name where the UPS is connected (e.g. bus="002" or bus="00[2-3]") as seen on Linux in /sys/bus/usb/devices or lsusb(8); including leading zeroes. ๐ŸšŒ

Note โ€” bus numbers are not guaranteed by the OS to be stable across re-boots, kernel driver reloads or device re-plugging (e.g. changing visible population of USB hubs). so like, don't build your whole personality on them ๐Ÿ’€
  • device = regex โ€” OPTIONAL, NOT RECOMMENDED.

select a UPS on a specific USB device or group of devices. the argument is a regular expression that must match the device name where the UPS is connected (e.g. device="001" or device="00[1-2]") as seen on Linux in /sys/bus/usb/devices or lsusb(8); including leading zeroes.

Note โ€” device numbers are not guaranteed by the OS to be stable across re-boots or device re-plugging. same energy as above, bestie ๐Ÿ˜ญ
  • busport = regex โ€” OPTIONAL, NOT RECOMMENDED.

if supported by the hardware, OS and libusb on the particular deployment, this option should allow you to specify physical port numbers on an USB hub, rather than logical device enumeration values โ€” and in turn, this should be less volatile across reboots or re-plugging. the value may be seen in the USB topology output of lsusb -tv on systems with that tool, for example. ๐Ÿ”Œ

Note โ€” this option is not practically supported by some NUT builds (it should be ignored with a warning then), and not by all systems that NUT can run on. so, you know. sometimes she's just not there ๐Ÿซ 
  • allow_duplicates โ€” OPTIONAL, NOT RECOMMENDED.

if you have several UPS devices which may not be uniquely identified by the options above (e.g. only VID:PID can be discovered there), this flag allows each driver instance where it is set to take the first match if available, or proceed to try another.

normally the driver initialization would abort at this point claiming "Resource busy" or similar error, assuming that the otherwise properly matched device is unique โ€” and some other process already handles it.

Warning โ€” this feature is inherently non-deterministic! the association of driver instance name to actual device may vary between runs! like, chaos mode activated, you have been warned ๐Ÿ’€๐Ÿ”ฅ

If you only care to know that at least one of your no-name UPSes is online, this option can help. ๐Ÿ’…

If you must really know which one โ€” it will not! ๐Ÿ˜ญ

  • usb_set_altinterface = bAlternateSetting โ€” force a redundant call to usb_set_altinterface(). Highkey useful when your device is out here serving multiple USB roles and the UPS isn't sitting on interface number 0 (which is the default).
  • usb_config_index, usb_hid_rep_index, usb_hid_desc_index, usb_hid_ep_in, usb_hid_ep_out โ€” force the use of specific interface / endpoint / descriptor index etc. numbers instead of just defaulting to 0 (some drivers for certain devices known to use non-zero numbers rarely land on other values). You write these as a hexadecimal number. ๐Ÿ”ข

As a rule of thumb for usb_hid_desc_index discovery: you'll see larger wDescriptorLength values (roughly 600+ bytes) in the reports from lsusb or similar tools. ๐Ÿ‘€

  • LIBUSB_DEBUG = INTEGER โ€” run-time troubleshooting of USB-capable NUT drivers isn't just about cranking up the common NUT debug verbosity (like using the DEBUG_MIN setting in ups.conf(5), or protocol commands to change the driver.debug value) โ€” it can also benefit from LibUSB-specific debugging. ๐Ÿ›

For that latter bit, you can set the LIBUSB_DEBUG driver option. Alternatively you can do it the classic way and export the environment variable LIBUSB_DEBUG before starting a NUT driver program (it may be set and "exported" in the driver init script or service method, perhaps via nut.conf(5)), to a numeric value such as 4 ("All messages are emitted").

For more details, including the currently supported values for your version of the library, see e.g.:

  • subdriver = string โ€” pick a serial-over-USB subdriver to use. Your choices are ablerex, armac, cypress, fabula, fuji, gtec, hunnox, ippon, krauler, phoenix, phoenixtec, sgs and snr. โœจ

Run the driver program with the --help option to see the exact list of subdriver values it would currently recognize.

Note ๐Ÿ“Œ When you use this option, it is mandatory to also specify the vendorid and productid matching parameters. No skipping, bestie.
  • langid_fix = value โ€” apply the language ID workaround to the krauler subdriver. This is mandatory for some devices to even work (LDLC, Dynamix and others). You must provide value (0x409 or 0x4095), according to your device entry in the NUT hardware compatibility list (HCL). ๐ŸŽ€
  • noscanlangid โ€” if this flag is set, don't autoscan the valid range for langid.

๐Ÿง  IMPLEMENTATION NOTES ๐Ÿง 

armac subdriver

The Armac communication subdriver reproduces a communication protocol used by an old release of "PowerManagerII" software, which doesn't seem to be Armac specific: its banner is "2004 Richcomm Technologies, Inc. Dec 27 2005 ver 1.1." Maybe other Richcomm UPSes would work with this โ€” maybe even better than with the older standalone richcomm_usb driver. ๐Ÿค”

fabula subdriver

This subdriver, meant to be used with the megatec protocol, does not support the various test.battery commands. Plus, the shutdown.return command ignores the values set in ups.delay.start/ondelay and makes the UPS turn on the load as soon as power is back. ๐Ÿ˜ฌ

gtec subdriver

Currently, the Gtec specific support is only known to work with USB devices (tested with a Gtec ZP120N), and was not seen with Serial port.

This mode is not automatically detected, and should be enabled manually in your ups.conf, e.g.:

[gtec-ups]
    driver = "nutdrv_qx"
    port = "auto"
    subdriver = "gtec"
    protocol = "gtec"

Other subdrivers and protocol implementations (including blazer_usb(8)) sort of work, but both have two problems:

  • They use the simple "Q1" query, which doesn't report the result of the latest battery test.
  • For some reason the UPS reports normal battery voltage even when the battery is completely disconnected. So you won't know the battery is dead until a power failure. ๐Ÿ’€
  • This driver sends the more advanced "Q4" request instead. Here the answer includes status letters with more information than the Q1 binary flags, including battery status.
  • USB reply is read in 8-byte chunks, which causes the UPS to disconnect from USB. The UPS reconnects in a second, but it still breaks the initialization of nutdrv_qx, where the query is sent twice in a short time (unlike blazer_usb).
    • The solution is simple: read the whole reply at once. ๐Ÿซถ

hunnox subdriver

This protocol subdriver is closely related to the fabula one, with a few tweaks for devices not directly supported by that driver.

fuji subdriver

This subdriver, meant to be used with the megatec protocol, does not support the shutdown.stayoff and load.off commands. Plus, the shutdown.return command ignores the values set in ups.delay.start/ondelay and makes the UPS turn on the load as soon as power is back. ๐Ÿ˜ญ

krauler subdriver

This subdriver, meant to be used with the megatec protocol, does not support the shutdown commands, i.e.: shutdown.return, shutdown.stayoff and load.off.

snr subdriver

This subdriver, meant to be used with the megatec protocol, does not support the shutdown commands, i.e.: shutdown.return, shutdown.stayoff and load.off.


โšก UPS COMMANDS โšก

This driver supports some instant commands (see upscmd(8)):

  • beeper.toggle โ€” toggle the UPS beeper. (Not available on some hardware) ๐Ÿ””
  • load.on โ€” turn on the load immediately. (Not available on some hardware)
  • load.off โ€” turn off the load immediately (see KNOWN PROBLEMS). โš ๏ธ
  • shutdown.return โ€” turn off the load and return when power is back. Uses the timers defined by ups.delay.start and ups.delay.shutdown.
  • shutdown.stayoff โ€” turn off the load and remain off (see KNOWN PROBLEMS). Uses the timer defined by ups.delay.shutdown. โš ๏ธ
  • shutdown.stop โ€” stop a shutdown in progress.
  • test.battery.start.deep โ€” perform a long battery test. (Not available on some hardware)
  • test.battery.start.quick โ€” perform a quick (10 second) battery test.
  • test.battery.stop โ€” stop a running battery test. (Not available on some hardware)

BESTUPS, INNOVART31, INNOVART33, INNOVATAE, MECER, MEGATEC, MEGATEC/OLD, MUSTEK, Q1, Q2, Q6, ZINTO PROTOCOLS

  • test.battery.start value โ€” perform a battery test for the duration of value seconds (truncated to 60 seconds) [60..5940].

MASTERGUARD PROTOCOL

  • clear.fault.record โ€” clear fault/error record ๐Ÿงน
  • beeper.enable โ€” enable the UPS beeper.
  • beeper.disable โ€” disable the UPS beeper.
  • test.battery.start.low โ€” perform a battery test until the battery charge is low.

The difference between the "battery test until battery low" and "deep battery test" is that the latter is actually a battery calibration test and needs some preconditions to be met, i.e. the load must be between 30% and 100% and the starting battery capacity is greater than 99%. ๐Ÿ“Š

The "Battery test until battery low" can be started anytime. โœจ

Feature was tested on Masterguard A1000 and A2000 units.

  • test.battery.start value โ€” perform a battery test for the duration of value seconds (truncated to 60 seconds) [0..5940]. This value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds (more than 60 seconds).
  • bypass.start โ€” put the UPS in bypass mode
  • bypass.stop โ€” take the UPS in normal mode

VOLTRONIC POWER P98 UNITS (WITH MECER PROTOCOL)

test.battery.start value

Perform a battery test for the duration of value seconds (truncated to 60 seconds) [12..5940]. This value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds (more than 60 seconds).

VOLTRONIC PROTOCOL

The following instant commands are available for the voltronic protocol. Not all of them are available on all the UPSes supported by this protocol. ๐Ÿ‘‘

  • beeper.enable โ€” enable the UPS beeper.
  • beeper.disable โ€” disable the UPS beeper.
  • test.battery.start value โ€” perform a battery test for the duration of value seconds [12..5940]. This value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds (more than 60 seconds).
  • outlet.1.load.off โ€” turn off outlet 1 load immediately.
  • outlet.1.load.on โ€” turn on outlet 1 load immediately.
  • outlet.2.load.off โ€” turn off outlet 2 load immediately.
  • outlet.2.load.on โ€” turn on outlet 2 load immediately.
  • outlet.3.load.off โ€” turn off outlet 3 load immediately.
  • outlet.3.load.on โ€” turn on outlet 3 load immediately.
  • outlet.4.load.off โ€” turn off outlet 4 load immediately.
  • outlet.4.load.on โ€” turn on outlet 4 load immediately.
  • bypass.start โ€” put the UPS in ECO Mode.
  • bypass.stop โ€” take the UPS out of ECO Mode.

๐Ÿ”ฎ BATTERY CHARGE GUESSTIMATION ๐Ÿ”ฎ

okay so bestie, by popular demand (yes, the people begged), this driver will report a guesstimated battery.charge and, if you want it, battery.runtime too โ€” but ONLY if you specified a couple of those EXTRA ARGUMENTS we just talked about. it's giving โœจmathโœจ and honestly we love her for it.

So if you drop both battery.voltage.high and battery.voltage.low into ups.conf(5), but you don't enter runtimecal, she's gonna guesstimate the state of charge by just looking at the battery voltage alone. and ngl, that is NOT reliable under load ๐Ÿ˜ญ because it only gives you reasonably accurate readings if you disconnect the load, let the battery rest for a couple minutes, and then measure the open cell voltage. which isโ€ฆ literally not practical when the power already went out and the UPS is busy powering your systems?? like be so fr. ๐Ÿ™ˆ

                        battery.voltage - battery.voltage.low
   battery.charge =  ------------------------------------------ x 100 %
                     battery.voltage.high - battery.voltage.low

There is a way to get better readings without disconnecting the load, but it requires you to keep track of how much (and how fast) current is going in and out of the battery. If you specified the runtimecal, the driver will attempt to do exactly that. but heads up โ€” this heavily relies on the values you enter, and the UPS must be able to report the load as well. and there are quite a couple of devices out there that report 0 % (or literally any other fixed value) at all times, in which case this obviously doesn't work. ๐Ÿ’€

The driver also has no way of determining the degradation of the battery capacity over time, so you'll have to deal with this yourself (by adjusting the values in runtimecal). Also note that the driver guesses the initial state of charge based on the battery voltage, so this may be less than 100 %, even when you are certain that they are full. there is just no way to reliably measure this between 0 and 100 % full charge. that's the tea. ๐Ÿซ–

This is better than nothing (but not by much). If any of the above calculations is giving you incorrect readings, you are the one that put in the values in ups.conf(5), so don't complain with the author. ๐Ÿ˜ค If you need something better, buy a UPS that reports battery.charge and battery.runtime all by itself without the help of a NUT driver. periodt. ๐Ÿ‘‘


๐Ÿ’ซ NOTES FOR THE PREVIOUS USER OF MEGATEC DRIVERS ๐Ÿ’ซ

The nutdrv_qx driver having replaced the megatec ones, some configuration changes may be required by users switching to nutdrv_qx.

Part of this, the following megatec options, in ups.conf(5), have to be changed:

  • battvolts โ€” You need to use default.battery.voltage.high and default.battery.voltage.low
  • dtr and rts โ€” You need to use cablepower
  • ignoreoff โ€” This parameter can simply be discarded, since it was a wrong understanding of the specification.

๐Ÿฆ‹ NOTES FOR THE PREVIOUS USER OF BLAZER DRIVERS ๐Ÿฆ‹

The nutdrv_qx driver having replaced the blazer ones, some configuration changes may be required by users switching to nutdrv_qx.

Part of this, the following blazer options, in ups.conf(5), have to be changed:

  • ondelay โ€” While the previous blazer drivers expected minutes, the new nutdrv_qx driver wants seconds.

The following instant command has also been changed:

  • test.battery.start value โ€” While the old blazer drivers expected a value in minutes, the nutdrv_qx driver wants a value in seconds.

๐ŸŒธ NOTES FOR THE PREVIOUS USER OF BESTUPS DRIVER ๐ŸŒธ

The nutdrv_qx driver having replaced the bestups one, some configuration changes may be required by users switching to nutdrv_qx.

Part of this, the following bestups options, in ups.conf(5), are no longer supported by this driver:

  • nombattvolt, battvoltmult โ€” See BATTERY CHARGE GUESSTIMATION.
  • ID โ€” Discarded.

๐Ÿงš NOTES FOR THE PREVIOUS USER OF VOLTRONIC DRIVERS ๐Ÿงš

The nutdrv_qx driver having replaced the voltronic ones, some configuration changes may be required by users switching to nutdrv_qx.

Part of this, the following voltronic options, in ups.conf(5), have to be changed:

  • ondelay โ€” While the previous voltronic drivers expected minutes, the new nutdrv_qx driver wants seconds. It no longer defaults to 0 minutes but to 3 minutes (i.e. 180 seconds) for compatibility with the users switching from the old blazer drivers.
  • battnumb โ€” This option has been renamed to battery_number.

The following options are no longer supported by this driver, you can now change them more conveniently "on the fly" calling upsrw(8) with the appropriate NUT variable โ€” provided that your UPS supports them. ๐Ÿ‘‡

  • battpacks โ†’ battery.packs โ€” Set number of battery packs in parallel [1..99]. This setting will change the charge and runtime estimation reported by the UPS.
  • battlow โ†’ battery.voltage.low โ€” Set minimum battery voltage just before the UPS automatically shuts down. This setting will change the charge and runtime estimation reported by the UPS.
  • auto_reboot โ†’ ups.start.auto โ€” Enable or disable auto reboot [enabled/disabled]. If enabled, the UPS will auto recover when AC power returns.
  • battery_protection โ†’ battery.protection โ€” Enable or disable battery deep discharge protection [enabled/disabled].
  • energy_saving โ†’ battery.energysave โ€” Enable or disable Green power function [enabled/disabled]. If enabled, for energy saving, the UPS will auto off when there is no load.
  • cold_start โ†’ ups.start.battery โ€” Enable or disable Cold Start [enabled/disabled]. If enabled, the UPS can be turned on also if AC is not connected to the UPS.
  • outlet_control โ†’ outlet.0.switchable โ€” Enable or disable programmable outlets control at battery mode [enabled/disabled]. If enabled, the UPS will cut off programmable outlets after backup time (set through outlet.{1,2,3,4}.delay.shutdown) arrives. If disabled, the UPS will provide continuous power to programmable outlets until the battery is running out.
  • max_eco_volt โ†’ input.transfer.high โ€” Maximum voltage for ECO Mode (V). If AC voltage is within acceptable range, ECO mode will be used (If the UPS is capable of and it's enabled).
  • min_eco_volt โ†’ input.transfer.low โ€” Minimum voltage for ECO Mode (V). If AC voltage is within acceptable range, ECO mode will be used (If the UPS is capable of and it's enabled).
  • max_eco_freq โ†’ input.frequency.high โ€” Maximum frequency for ECO Mode (Hz). If AC frequency is within acceptable range, ECO mode will be used (If the UPS is capable of and it's enabled).
  • min_eco_freq โ†’ input.frequency.low โ€” Minimum frequency for ECO Mode (Hz). If AC frequency is within acceptable range, ECO mode will be used (If the UPS is capable of and it's enabled).
  • outlet1_delay โ†’ outlet.1.delay.shutdown โ€” Delay time before programmable outlet 1 shuts down the load when on battery mode [0..59940] (seconds).
  • outlet2_delay โ†’ outlet.2.delay.shutdown โ€” Delay time before programmable outlet 2 shuts down the load when on battery mode [0..59940] (seconds).
  • outlet3_delay โ†’ outlet.3.delay.shutdown โ€” Delay time before programmable outlet 3 shuts down the load when on battery mode [0..59940] (seconds).
  • outlet4_delay โ†’ outlet.4.delay.shutdown โ€” Delay time before programmable outlet 4 shuts down the load when on battery mode [0..59940] (seconds).
  • batt_type โ†’ battery.type โ€” Battery type (for P31 UPSes only) [Li/Flooded/AGM].

๐Ÿ’€ KNOWN PROBLEMS ๐Ÿ’€

ok so bestie, here's the tea on stuff that lowkey doesn't work everywhere ๐Ÿซ 

Some UPS commands just aren't supported by all models. Like, it's not a universal thing. In most cases, the driver will send a message to the system log when the user tries to execute an unsupported command โ€” so at least you get some kind of heads up, yk? But unfortunately, some models don't even provide a way for the driver to check for this, so the unsupported commands will silently fail. And by silently I mean SILENTLY. no log, no nothing, just vibes and disappointment ๐Ÿ˜ญ

Both the load.off and shutdown.stayoff instant commands are meant to turn the load off indefinitely. That's the whole point of them, that's their main character arc. However, some UPS models don't allow this. so like. don't count on it everywhere fr fr.

Some models report a bogus value for the beeper status (will always be enabled or disabled). So the beeper.toggle command may appear to have no effect in the status reported by the driver when, in fact, it is working fine. it's giving gaslighting honestly ๐Ÿ’… the UPS is fine, the reporting is the problem.

The temperature and load value is known to be bogus in some models. yeah. those numbers? not real. ๐Ÿ™ˆ


MASTERGUARD UNITS

The driver is supposed to support both "new" A series (A700/1000/2000/3000 and their -19 cousins) and E series (E60/100/200), but was tested only on A due to lack of E hardware. so like, E series is theoretically supported, we just never got our hands on one to vibe check it ๐Ÿงš no cap.


VOLTRONIC-AXPERT UNITS

This protocol supports Voltronic Power Axpert inverters, based on P30 protocol (used e.g. in photovoltaic equipment, often paired with an UPS charged by the solar panels). โ˜€๏ธ๐Ÿ”‹ iconic combo honestly.

The code is currently largely experimental, with data point and command names not aligned with concepts that are part of NUT standard vocabulary (this many of them are prefixed with experimental. namespace). In fact, many features may be only exposed in specially configured builds of the NUT driver program. so like โ€” don't be shocked when the names look weird, that's on purpose โœจ


VOLTRONIC-QS UNITS

Both load.off and shutdown.stayoff instant commands are known to work as expected (i.e. turn the load off indefinitely) only if mains is present. Otherwise, as soon as mains returns, the load will be powered. so the "indefinitely" part is doing a lot of heavy lifting there ๐Ÿ˜ญ

After issuing a shutdown.return instant command, the UPS won't wait ondelay before powering on the load, provided the following conditions are met:

  • if the load has been previously (no matter how long before) powered off through load.off/shutdown.stayoff and powered on through load.on/shutdown.stop, and
  • if AC wasn't cut after issuing the load.off/shutdown.stayoff (i.e. the UPS didn't turn itself off), and
  • if there's a power outage after issuing the shutdown.return command

In this case, as soon as mains returns the load will be powered. like, immediately. no waiting, no ondelay, nothing. just bam โšก


VOLTRONIC-QS-HEX UNITS

shutdown.return, load.off, and shutdown.stayoff instant commands are known to work as expected only if mains is present. Otherwise, as soon as mains returns, the load will be powered. same energy as the QS ones above tbh ๐Ÿ’€


๐Ÿšจ UPS WARNINGS (VOLTRONIC PROTOCOL) ๐Ÿšจ

ok this part is actually so cool once you get it, stay with me ๐Ÿซถ

The UPSes supported by voltronic protocol report warnings through a 64bit flag (bit1bit2...bit63bit64) where 1 means that a warning arose, while 0 means no warning. It's giving bitmask core. ๐Ÿ‘‘

Since more than one warning at a time can be signaled, and because of the limited space in the ups.alarm variable, if the length of the warnings exceeds that of ups.alarms variable, they will be reported as bits. so sometimes you don't get the nice human sentence โ€” you get the raw bits, bestie.

If you want to know the explanation of that bit you can either watch the log or see the next table (unlisted bits equal to unknown warnings). the table's coming right up, don't you worry ๐Ÿ’–


๐Ÿ‘‘ Table 1. UPS Warnings for voltronic UPSes ๐Ÿ‘‘

okay so this is the big one, the warning bingo card ๐ŸŽ€ every single entry in the table, in order, nothing skipped, nothing summarised. The number on the left is the index, and the text next to it is the corresponding warning you're gonna see. Save this list, screenshot it, tattoo it on your forearm, idk, but it's here ๐Ÿ’–

  1. Battery disconnected
  2. Neutral not connected
  3. Site fault
  4. Phase sequence incorrect
  5. Phase sequence incorrect in bypass
  6. Input frequency unstable in bypass
  7. Battery overcharged
  8. Low battery
  9. Overload alarm
  10. Fan alarm
  11. EPO enabled
  12. Unable to turn on UPS
  13. Over temperature alarm
  14. Charger alarm
  15. Remote auto shutdown
  16. L1 input fuse not working
  17. L2 input fuse not working
  18. L3 input fuse not working
  19. Positive PFC abnormal in L1
  20. Negative PFC abnormal in L1
  21. Positive PFC abnormal in L2
  22. Negative PFC abnormal in L2
  23. Positive PFC abnormal in L3
  24. Negative PFC abnormal in L3
  25. Abnormal in CAN-bus communication
  26. Abnormal in synchronous signal circuit
  27. Abnormal in synchronous pulse signal circuit
  28. Abnormal in host signal circuit
  29. Male connector of parallel cable not connected well
  30. Female connector of parallel cable not connected well
  31. Parallel cable not connected well
  32. Battery connection not consistent in parallel systems
  33. AC connection not consistent in parallel systems
  34. Bypass connection not consistent in parallel systems
  35. UPS model types not consistent in parallel systems
  36. Capacity of UPSs not consistent in parallel systems
  37. Auto restart setting not consistent in parallel systems
  38. Battery cell over charge
  39. Battery protection setting not consistent in parallel systems
  40. Battery detection setting not consistent in parallel systems
  41. Bypass not allowed setting not consistent in parallel systems
  42. Converter setting not consistent in parallel systems
  43. High loss point for frequency in bypass mode not consistent in parallel systems
  44. Low loss point for frequency in bypass mode not consistent in parallel systems
  45. High loss point for voltage in bypass mode not consistent in parallel systems
bestie if you're seeing like half of these at once, that's not a vibe check, that's an โœจemergencyโœจ. Forty-five ways to be sad, and the parallel-system ones all start sounding the same after a while โ€” which is lowkey the point, they're all "one of your units disagrees with the others" energy ๐Ÿ˜ญ

and we're not done, keep going ๐Ÿ’…

  • 46 โ€” Low loss point for voltage in bypass mode not consistent in parallel systems
  • 47 โ€” High loss point for frequency in AC mode not consistent in parallel systems
  • 48 โ€” Low loss point for frequency in AC mode not consistent in parallel systems
  • 49 โ€” High loss point for voltage in AC mode not consistent in parallel systems
  • 50 โ€” Low loss point for voltage in AC mode not consistent in parallel systems
  • 51 โ€” Warning for locking in bypass mode after 3 consecutive overloads within 30 min
  • 52 โ€” Warning for three-phase AC input current unbalance
  • 53 โ€” Warning for a three-phase input current unbalance detected in battery mode
  • 54 โ€” Warning for Inverter inter-current unbalance
  • 55 โ€” Programmable outlets cut off pre-alarm
  • 56 โ€” Warning for Battery replace
  • 57 โ€” Abnormal warning on input phase angle
  • 58 โ€” Warning!! Cover of maintain switch is open
  • 62 โ€” EEPROM operation error

๐Ÿซถ AUTHORS

the literal icons who built this. show some respect bestie ๐Ÿ’–

  • Daniele Pezzini <hyouko@gmail.com>
  • Arnaud Quette <arnaud.quette@gmail.com>
  • John Stamp <kinsayder@hotmail.com>
  • Peter Selinger <selinger@users.sourceforge.net>
  • Arjen de Korte <adkorte-guest@alioth.debian.org>
  • Alexander Gordeev <lasaine@lvk.cs.msu.su>
  • Edgar FuรŸ <ef@math.uni-bonn.de>