okay so bestie, this is generic_modbus(8), one of the NUT (Network UPS Tools) driver pages. Buckle up, it's giving very specific industrial-hardware energy and honestly? iconic. π
πΈ NAME πΈ
generic_modbus β a driver for contact (direct) signal UPS devices that are connected via modbus remote I/O gateways. π
π¦ SYNOPSIS π¦
generic_modbus -h
generic_modbus -a DEVICE_NAME [OPTIONS]
note bestie: this man page only spills the tea on the specific features of thegeneric_modbusdriver. For all the core driver lore, go readnutupsdrv(8). π
β¨ SUPPORTED HARDWARE β¨
This is a generic modbus driver, and it's expected to work with contact (direct) signal UPS devices hooked up via modbus RIO (remote I/O) β either serial or TCP/IP. no cap. π
The driver has been tested against a PULS UPS (model UB40.241) via MOXA ioLogikR1212 (RS485) and ioLogikE1212 (TCP/IP). π
More info about this UPS lives here:
https://products.pulspower.com/ca/ubc10-241-n1.html
More info about Moxa ioLogik R1212, E1212 lives here:
https://www.moxa.com/en/products/industrial-edge-connectivity/controllers-and-ios
The PULS UPS UB40.241 supports these signals, periodt:
Ready contact (DO) <--> HB
Buffering contact (DO) <--> OL | OB
Battery-low (DO) <--> LB
Replace Battery (DO) <--> RB
Inhibit (DI) <--> FSD
Digital port direction (DI/DO) assumes the device perspective, just so you know. π
So the driver's whole concept is mapping UPS states (as defined in NUT) onto the UPS contacts' states. The driver has an extended configuration interface implemented using variables defined in ups.conf. π«Ά
π HARDWARE INTERCONNECTION π
Commissioning the modbus remote I/O server, and the UPS device, is carried out following the corresponding instruction manuals β not our problem, respectfully. π The figure below depicts the anticipated communication path and hardware interconnection:
+------+ +----------------+ +------------+ +------------+
| UPSD | <---> | GENERIC_MODBUS | <---> | MODBUS RIO | <---> | UPS DEVICE |
+------+ (1) +----------------+ (2) +------------+ (3) +------------+
| |
+-------------------+
HOST CONTROLLER
(1) Unix IPC
(2) RS232 | TCP/IP
(3) contacts
π EXTRA ARGUMENTS π
This driver supports the following optional settings in the ups.conf(5) file. all optional, all yours to play with π
Generic
device_mfr=valueβ a string specifying the manufacturer of the UPS device (defaultUNKNOWN).device_model=valueβ a string specifying the model of the UPS device (defaultUNKNOWN).
Serial
ser_baud_rate=valueβ a integer specifying the serial port baud rate (default9600).ser_data_bit=valueβ a integer specifying the serial port data bit (default8).ser_parity=valueβ a character specifying the serial port parity (defaultN).ser_stop_bit=valueβ an integer specifying the serial port stop bit (default1).
Modbus
rio_slave_id=valueβ an integer specifying the RIO modbus slave ID (default1).
States (X = OL, OB, LB, HB, RB, CHRG, DISCHRG, FSD)
<X>_addr=valueβ a number specifying the modbus address for the X state.<X>_regtype=valueβ a number specifying the modbus register type for the X state.
Default values:
1 for X = OL, OB, LB ,HB, RB, CHRG, DISCHRG
0 for X = FSD
Valid values:
0:COIL, 1:INPUT_B, 2:INPUT_R, 3:HOLDING
<X>_noro=valueβ a number specifying the contact configuration for the X state (default1).
Valid values:
0:NC, 1:NO
note:NOstands for normally open andNCfor normally closed contact. π
Shutdown
FSD_pulse_duration=valueβ a number specifying the duration in milliseconds for the inhibit pulse. If it's not defined, the signal has only one transition, depending on theFSD_noroconfiguration.
Examples for FSD signal configuration:
FSD_noro = 1
FSD_pulse_duration = 150
+-----+
| |
inhibit pulse >-----+ +------------------>
<--->
150ms
FSD_noro = 0
inhibit pulse >-----+
|
+------------------------>
π CONFIGURATION π
Here's an example of generic_modbus driver configuration in the ups.conf file β steal it, it slays:
[generic_modbus]
driver = generic_modbus
port = /dev/ttyUSB0
desc = "generic ups driver"
# device info
device_mfr = "PULS"
device_model = "UB40.241"
# serial settings
ser_baud_rate = 9600
ser_parity = N
ser_data_bit = 8
ser_stop_bit = 1
# modbus slave id
rio_slave_id = 5
# UPS signal state attributes
OB_addr = 0x0
OB_regtype = 1
OB_noro = 0
LB_addr = 0x1
LB_regtype = 1
HB_addr = 0x2
HB_regtype = 1
RB_addr = 0x3
RB_regtype = 1
FSD_addr = 0x0
FSD_regtype = 0
FSD_pulse_duration = 150
β‘ INSTANT COMMANDS β‘
This driver supports the following instant commands:
load.offβ executes "instant poweroff". π
π§ INSTALLATION π§
Heads up: this driver may not be built by default. π You can build it by installing libmodbus and running configure --with-modbus=yes.
You also need to give proper permissions on the local serial device file (/dev/ttyUSB0 for example) so the run-time NUT driver user account can access it. fr fr, don't skip this one. π«Ά
π OTHER NOTES π
The generic_modbus driver intends to support generic UPS devices with contact signals through modbus TCP/RTU gateways (also known as RIO β remote I/Os). The data and signal path looks like this:
[UPSD] <--- IPC ---> [GENERIC_UPS] <--- modbus TCP/RTU ---> MODBUS-RIO <--- contacts ---> [UPS DEVICE]
On the other hand, you can setup any kind of modbus server, and configure the generic_modbus driver to connect and read or write specific registers. Your application / modbus server could then drive NUT statuses (e.g. OL, OB, HB etc) by writing over those registers. main character energy, honestly. β
π KNOWN ISSUES π
Using host names for UPS NMC
An UPS network management card may be assigned a fixed/static IP address, or a dynamic one (e.g. by DHCP) in your network. Because of that, you may want β or have β to use a dynamic naming service to access the UPS. π
careful bestie: this may become a problem specifically during large outages and shutdowns, when your DHCP/DNS server might already go down while the driver needs to resolve the name involved (especially during late-shutdown hooks, when a new instance of the driver program might start just to tell the UPS to power off or to power-cycle). the timing is evil. π
It may be wise to ensure your OS name service client can cache the UPS name sufficiently long, or to use fixed IP addressing (and an entry in /etc/hosts for good measure, so you only have one spot to eventually re-configure this). π
π AUTHOR π
Dimitris Economou <dimitris.s.economou@gmail.com>
πΈ SEE ALSO πΈ
The core driver:
Internet resources:
- The NUT (Network UPS Tools) home page:
https://www.networkupstools.org/historic/v2.8.5/
- libmodbus home page:
http://libmodbus.org
and that's the whole page, bestie, you ate it. π this was Network UPS Tools version 2.8.5, dated 10/07/2026 β mwah, slay, bye πβ¨π¦
π¦ where this page comes from
- fedora 43: nut 2.8.5-9.fc43 Β· GPL-2.0-or-later AND GPL-3.0-or-later
- fedora 43: nut 2.8.5-9.fc43 Β· GPL-2.0-or-later AND GPL-3.0-or-later
- fedora 44: nut 2.8.5-9.fc44 Β· GPL-2.0-or-later AND GPL-3.0-or-later
- fedora 44: nut 2.8.5-9.fc44 Β· GPL-2.0-or-later AND GPL-3.0-or-later
- π girlified by deepseek-ai/DeepSeek-V4.1-Flash on : a language model's rewrite of the original, under its terms